Fire Department Test Questions and Verified Answers |
Latest Update 2026/2027 | 100% Correct
1. Operating devices
Answer Shall operate at 32F to 120F
2. Manual actuators force
Answer Shall not have a force more than 40lbs
3. Pipe and fittings material
Answer Shall be made of non-combustible materials
4. Pipe and fittings type
Answer Galvanized pipe and fittings
5. Assembly examination of pipe
Answer Shall be examined internally to detect and remove
contaminants
6. Location of manual actuators
, Answer Shall be located in a path of egress
7. Manual actuators installation height
Answer Shall be installed no more than 48in and no less than 42in
8. Fusible links location
Answer Shall be located above each cooking appliance
9. Manual actuators movement
Answer Shall not have a movement of more than 14 inches
10. Instructions with pictographs and
lettering Answer Shall be at least 1/4
inches
11. Fusible links distance
Answer Shall be 12 in in front of said item
12. Hydrostatic testing of piping