There are 6 conductors in a raceway connected to 70 deg rated circuit breaker. Each wire has a 70amp
load using THHN conductors. The Minimum size conductors used are #________AWG. - correct
answers4, 310.15(B)(16)
Thermal insulation shall not be installed within __________ inches of recessed lighting fixtures. - correct
answers3", 410.116(B)
A 1" conduit contains three 3-wire circuits or a phase system. All conductors are #10TW. Each circuit
consists of two-phase conductors and one grounded conductor and one equipment grounding
conductor. The maximum ampacity of each phase conductor is __________. - correct answers24A,
310.15(B)(16)
The volt/ampere rating of a device that consumes 14.5 amperes on a 240 volt circuit is______________.
- correct answers3480W, P=IxE. 240 x 14.5 = 3480
A 208volt, 3 phase heater draws 3,598 watts. How many amperes does the heater draw? - correct
answers10A, P=E x 1.73/I. I=3598/359.84
An underwater light fixture shall be installed at least __________ inches below the water level? - correct
answers18", 680.23(5)
A general-purpose receptacle shall not be installed on the_____________. - correct answersFence -
Directly south of the pool. 680.22(A)(1)
A junction box for the 120 volt wet-niche fixture shall be at least_________inches above the ground? -
correct answers4", 680.24(A)(2)(a)
A GFCI protected___________receptacle for the pump motor maybe installed on the south side of the
dwelling unit dedicated grounding type. - correct answersdedicated receptacle, 680.22(A)(2)
, A metal fence installed with-in_________feet of the pool shall be bonded. - correct answers5', 680.26(B)
(7)
The feed to the wet-niche fixture shall be installed in _________? - correct answersRigid Brass,
680.23(B)(2)(a)
A 15 or 20 amp receptacle shall be located with-in____________feet of a roof top air conditioner? -
correct answers25', 210.63
The maximum over current protection for 8 current carrying #12 THHN conductors iterm-13n a 1/2"EMT
conduit is__________amps? - correct answers20A, 310.15(B)(16)
An AC system of 50 to 1000 volts shall be grounded if maximum voltage to ground does not exceed
______________ volts. - correct answers150, 250.20(B)(1)
There is a 10HP, 230volt, 3 phase motor, code letter G. the maximum standard rating inverse time circuit
breaker permitted to serve as branch circuit, short circuit, and ground fault protection when the motor
starts the load without difficulty is_____________amps? - correct answers70, 430.52-430.250
Type "S" adapters are installed in Edison base fuse holders___________? - correct answersTo limit the
size of the fuse to be installed, 240.53(B)
A laundry branch circuit shall be rated at ______________amps. - correct answers20, 210.11(C)(2)
In a commercial building the minimum size ungrounded service entrance conductor for 120/240 volt 1
phase 200 amp service is ___________. - correct answers3/0 THWN copper, 310.15(B)(16)
The minimum service for a one family dwelling shall be__________? - correct answers100A, 230.79(c)
Type _________ cable is not permitted for service entrance. - correct answersUF, 340,12(A)
A kiln rated 4750 watts, 208volt 3 phase draws __________ amps. - correct answers13.2A. I=P/E x 1.73