P-99 Low Pressure Boiler COF FDNY Newest
2025/2026 Complete 100 Questions And Correct
Detailed Answers (Verified Answers) |Newest Version!!
All heating, combustion, and cooking equipment shall be
provided with insulation or the building construction shall
be fire protected, so that during operation the surface of
combustible construction materials will not be raised to a
temperature higher than ____. - Answer-170 ̊ F
Acceptance tests: Boilers shall not be placed in operation
upon completion of construction until they have been ____
and an equipment use permit has been issued by the
commissioner. - Answer-Inspected and tested.
Periodic boiler inspections: All boilers shall be inspected at
least ____ including chimney connections. - Answer-Once
a year.
Owner's annual statement: The owner of each boiler that
is subject to periodic inspections shall file an annual ____
with the commissioner, specifying the location of each
boiler and arrangement for inspection. - Answer-Written
statement.
,2|Page
What three things must be tested for any fuel burning and
storage installation before the system can be operated? -
Answer-(1) Tightness of liquid fuel piping.
(2) Tightness of fuel oil storage tanks.
(3) Tightness of gas distribution piping.
What are instruction cards for oil burning systems? -
Answer-Cards giving complete instructions for care and
operation that are permanently located near the
equipment.
Every oil burning installation that is not fully automatic or
requires preheating shall be operated by, or under, the
direct supervision of a person holding a ____ issued by
the fire commissioner. - Answer-COF
After any fuel burning equipment repair for which a
licensed operator is required, such operator shall also
check the repairs and be ____ while the equipment is
started. - Answer-Present.
, 3|Page
What is abatement of air contaminants? - Answer-
Compliance with the air pollution control code.
What are the 3 equipment classifications and their
temperatures for the products of combustion at the point of
leaving the equipment? - Answer-(1) Low Temp: 600° F or
less.
(2) Medium Temp: 600° - 1000° F.
(3) High Temp: 1000° or greater.
Ventilation shall be capable of providing at least ____
CFM of air for each gallon of oil per hour required to fire
the equipment to gross output. - Answer-36
What is fuel-oil? - Answer-Hydrocarbon oils with a
flashpoint not lower than 100 ̊F.
The use of crankcase refuse oil as fuel-oil is ____. -
Answer-Prohibited.