Content preview

BICSI INSTALLER 1 STUDY GUIDE QUESTIONS AND
ANSWERS 2025/2026 ALL RATED A+
✔✔What type of fire stop systems are caulks, pads, and foams? - ✔✔Non-mechanical

✔✔Wall cavity boxes should be - ✔✔Mounted to a wall stud or other framing member
with suitable fasteners

✔✔The bandwidth of optical fiber can be decreased by - ✔✔Increasing the length of the
cable

✔✔What step should be performed FIRST when terminating a coaxial cable? -
✔✔Verify the connector type

✔✔How do firestops of elastomeric materials function? - ✔✔They are sized to fit the
opening being sealed and they swell around and within the penetration to provide a tight
seal

✔✔What is the MINIMUM inside bend radius for balanced twisted pair (4-pair) cable? -
✔✔10 times the outside diameter

✔✔After the installer has tested the equipment and verified the problem, what is the
NEXT step in the troubleshooting process - ✔✔Isolate the source

✔✔For a retrofit project, the installer should plan to verify the existing structure against
any documents received before engaging in a pull because - ✔✔The existing
documents may reflect moves, adds, and changes that took place in the initial
construction

✔✔Slack in a cable performs what vital function? - ✔✔Cable slack ensures there is
enough room for later terminations

✔✔What is the BEST description for racks and cabinets? - ✔✔Racks are vertical metal
frames, and cabinets can be considered enclosed racks

✔✔The first step to pulling horizontal cables in conduit is choosing a method of
establishing the cable run distance. However, when installing horizontal cable in open
ceiling, what is the FIRST step? - ✔✔Attach pull string to cables or pulling harness

✔✔Why is it important to maintain the MINIMUM bend radius during a cable pull? -
✔✔This precaution prevents potential damage to the cable that could impact its ability
to transmit signals

, ✔✔What is used to measure the length of a 4-pair cable? - ✔✔Time domain
reflectometer (TDR)

✔✔For the purpose of managing cables that extend from equipment within racks, racks
should be installed so that the cables run through the __________ of the rack - ✔✔Rear

✔✔What is the function of the shielding on STP cable? - ✔✔The shielding functions to
protect the signal from outside noise sources

✔✔This pathway type can be installed on walls, ceilings, modular furniture and modular
furniture panels. What type is it? - ✔✔Surface-mounted raceways

✔✔What is the LAST step in the process of installing a poke-through? - ✔✔Label the
poke-through device as required by contract documents and applicable standards

✔✔What fire-rating provides information about smoke penetration? - ✔✔L rating

✔✔Reviewing the work schedule, you see that you are scheduled to install a TE in a
free-standing piece of furniture. Why is this a problem? - ✔✔TEs should not be installed
in furniture unless the furniture is permanently secured to the building structure

✔✔You are MORE LIKELY to encounter ___________ dangers on a retrofit project
than on a new build - ✔✔Asbestos

✔✔When working with optical fiber cable, what shall be the slack left in the work area to
allow for termination? - ✔✔3.3 feet

✔✔The most common drawings installers will encounter on the job site are - ✔✔T
drawings

✔✔In many jurisdictions, this color is restricted for use on cabling associated with the
fire detection system. Which color is this? - ✔✔Red

✔✔What is an example of a fire barrier? - ✔✔Fire-rated floor

✔✔On sure you would expect to use ________ to route the cable though a conduit -
✔✔Pull strings

✔✔What tool is a low-cost cable verifier that can be used to test for open circuits, short
circuits, crossed pairs, and miswires in 4-pair cable? - ✔✔Wire map tester

✔✔ Of the four termination blocks, which one does not IDC in the base block? - ✔✔110
Block

Document information

Uploaded on
October 15, 2025
Number of pages
7
Written in
2025/2026
Type
Exam (elaborations)
Contains
Questions & answers
$12.49

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
Pyramids
4.0
(2)
Sold
22
Followers
4
Items
7208
Last sold
3 weeks ago



Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions