Troubleshooting Exam Newest / AWWA Backflow Prevention Assembly
Testing Key Procedures and Troubleshooting Exam Preparation/ AWWA
Backflow Prevention Assembly Testing Key Procedure
Containing a plumbing system from the public water supply requires
backflow protection at the _______?
A. Appliance or fixture
B. Building foundation
C. Irrigation system
D. Service Connection
E. Sprinkler riser - ANSWERService Connection
Backflow preventer manufacturers recommend that assemblies be field-
tested annually and when_____?
A. Installed
B. Moved
C. Repaired or Installed
D. Shut down
E. Water suppliers provide notice - ANSWERRepaired or Installed
A differential pressure gauge reading of 0.2 psid is represented on water
column sight tube by _____?
A. 1/16 in. (0.16 cm)
,B. 1/2 in. (1.3 cm)
C. 2 in. (5.1 cm)
D. 3.5 in. (8.9 cm)
E. 5.5 in. (14 cm) - ANSWER5.5 in. (14 cm)
Pollution of a public water supply suggests the substance in the water is
____?
A. Aesthetically bad
B. Biological with virus only
C. Lowering the pH below 1.4
D. Radiological
E. Toxic - ANSWERAesthetically bad
Backsiphonage may occur when the pressure inside copper tubing is ____?
A. Greater than atmospheric pressure
B. Greater than barometric pressure
C. Greater than 0 gauge pressure
D. Less than absolute pressure
E. Less than atmospheric pressure - ANSWERLess than atmospheric pressure
A cross-connection may be a permanent piping arrangement or a(n) ____?
A. Backflow preventer
B. Church symbol
C. OSHA hazardous area designation
D. Railroad and highway intersection sign
,E. Temporary hose bibb connection - ANSWERTemporary hose bibb
connection
The isolation of a plumbing water system hazard requires____?
A. Appliance protection
B. Building quarantine
C. High-hazard protection
D. Meter protection
E. Toxin monitoring - ANSWERAppliance protection
A direct cross-connection suggests the piping system may be subjected to
____?
A. Backpressure or backsiphonage
B. Backsiphonage only
C. Periodic inspection
D. Sustained pressure
E. Toxic materials - ANSWERBackpressure or backsiphonage
A pipe restriction's flow velocity increase may allow ____?
A. Aspiration
B. Backpressure
C. Low turbulence
D. Pressure head
E. Pressure surges - ANSWERAspiration
, Water supply contamination from backflow may result in ____?
A. A bad taste
B. Coloration
C. Death
D. Odor or smell
E. Pipe wall mineral deposit flaking - ANSWERDeath
To prevent backflow, an atmospheric vacuum breaker is primarily designed to
____?
A. Allow air into the outlet piping system
B. Create an elevation loop above ground
C. Introduce head loss
D. Prevent backpressure
E. Restrict velocity - ANSWERAllow air into the outlet piping system
Atmospheric vacuum breakers will typically be located on ____?
A. Commercial irrigation systems
B. Fire-suppression systems
C. Plumbing fixtures or appliances
D. Utility storage tanks
E. Water service connections - ANSWERPlumbing fixtures or appliances
The mechanical component of an atmospheric vacuum breaker serves as an
air-inlet valve and a ____?
A. Check valve