Medical Gas Certification Pre-test Solved
Exam Questions and Answers (Complete
Practice Papers)
An existing system that is not in strict compliance with the
provisions of this code shall be permitted to be continued in a
use as long as the __________ has determined that such use
does not constitute a distinct hazard to life.
A. Architect
B. Authority having jurisdiction
C. Engineer
D. Nursing - Correct Answers ✅B. Authority having
jurisdiction
Indoor locations for oxygen, nitrous oxide, and mixtures of
these gases shall not communicate with any of the following
except__________
A. Areas with open flames
B. Designated storage area
C. Engines
D. Kitchens - Correct Answers ✅B. Designated storage
area
An auxiliary source connection shall consist of all the
following except
A. Removable plug or cap
B. Tree
C. Valve
,Medical Gas Certification Pre-test Solved
Exam Questions and Answers (Complete
Practice Papers)
D. Visual pressure indicator - Correct Answers ✅D. Visual
pressure indicator
When multiple buildings are served from a single cryogenic
liquid oxygen source, it is required to place the emergency
oxygen supply connection in-
A. Each building served
B. The building closest to the source
C. The largest building served
D. The main building only - Correct Answers ✅A. Each
building served
The minimum clearance around the EOSC for a temporary
source of supply is ____________ ft.
A. 2
B. 3
C. 5
D. 6 - Correct Answers ✅B. 3
The quality medical air shall comply with all of the following
standards except
A. Be filtered to 0.01 microns
B. Have lesson than 25 ppm gaseous hydrocarbons
, Medical Gas Certification Pre-test Solved
Exam Questions and Answers (Complete
Practice Papers)
C. Have no detectable liquid hydrocarbons
D. Meet the requirement of medical air USP - Correct
Answers ✅A. Except be filtered to 0.01 microns
Medical air sources shall only be use for _____
A. Air operating devices
B. Human respiratory applications
C. Instrument air
D. WAGD - Correct Answers ✅B. Human respiratory
applications
Medical air filters shall be sized for 100% of the system peak
calculated demand and be rated for a minimum of 98%
efficiency at ______ micron greater.
A. .01
B. 1
C. 5
D. 10 - Correct Answers ✅B. 1
In a medical air supply system dryers, filters, and regulators
shall be.
A. At least duplexed
Exam Questions and Answers (Complete
Practice Papers)
An existing system that is not in strict compliance with the
provisions of this code shall be permitted to be continued in a
use as long as the __________ has determined that such use
does not constitute a distinct hazard to life.
A. Architect
B. Authority having jurisdiction
C. Engineer
D. Nursing - Correct Answers ✅B. Authority having
jurisdiction
Indoor locations for oxygen, nitrous oxide, and mixtures of
these gases shall not communicate with any of the following
except__________
A. Areas with open flames
B. Designated storage area
C. Engines
D. Kitchens - Correct Answers ✅B. Designated storage
area
An auxiliary source connection shall consist of all the
following except
A. Removable plug or cap
B. Tree
C. Valve
,Medical Gas Certification Pre-test Solved
Exam Questions and Answers (Complete
Practice Papers)
D. Visual pressure indicator - Correct Answers ✅D. Visual
pressure indicator
When multiple buildings are served from a single cryogenic
liquid oxygen source, it is required to place the emergency
oxygen supply connection in-
A. Each building served
B. The building closest to the source
C. The largest building served
D. The main building only - Correct Answers ✅A. Each
building served
The minimum clearance around the EOSC for a temporary
source of supply is ____________ ft.
A. 2
B. 3
C. 5
D. 6 - Correct Answers ✅B. 3
The quality medical air shall comply with all of the following
standards except
A. Be filtered to 0.01 microns
B. Have lesson than 25 ppm gaseous hydrocarbons
, Medical Gas Certification Pre-test Solved
Exam Questions and Answers (Complete
Practice Papers)
C. Have no detectable liquid hydrocarbons
D. Meet the requirement of medical air USP - Correct
Answers ✅A. Except be filtered to 0.01 microns
Medical air sources shall only be use for _____
A. Air operating devices
B. Human respiratory applications
C. Instrument air
D. WAGD - Correct Answers ✅B. Human respiratory
applications
Medical air filters shall be sized for 100% of the system peak
calculated demand and be rated for a minimum of 98%
efficiency at ______ micron greater.
A. .01
B. 1
C. 5
D. 10 - Correct Answers ✅B. 1
In a medical air supply system dryers, filters, and regulators
shall be.
A. At least duplexed