The ASSE 6040 Standard applies to individuals who
_______________ medical gas and vacuum systems.
A install
B perform inspections of new installations
C maintain
D verify - Correct Answers ✅maintain
At sea level the atmospheric pressure is 14.7 psia. What
is the absolute pressure of a 50 psig (gauge pressure)
system at sea level?
A 64.7 psia
B 50 psia
C 34.7 psia
D 60 psia - Correct Answers ✅64.7 psia
Medical Gas _______________________________ shall be able
to describe how to find and implement manufacturer
specific maintenance requirements for the medical gas
and vacuum system components per ASSE 6000 Annex D
and CGA E.10.
A Supplier or Distributor
B Maintenance Personnel
C Authority having jurisdiction
,NFPA 99 6040 practice set Questions and
Verified Answers, 100% Score Guarantee
Pass (Latest 2025)
D Verifier or Inspector - Correct Answers
✅Maintenance Personnel
Medical Gas Maintenance Personnel shall be able to
identify and describe the hazards resulting from improper
maintenance of medical gas and vacuum systems,
including:
A Flow
B Cross Connections
C Contaminants
D All of the above - Correct Answers ✅All of the above
ASSE 6000 daily checks of bulk liquid systems include all
of the following with the exception of
______________.
A Primary and Reserve (if equipped) Tank Contents
B Pressure Dew Point Temperature
C Leaks or Unusual Icing
D Proper pressure maintained - Correct Answers
✅Pressure Dew Point Temperature
Per ASSE 6000 Annex D typical maintenance procedures
include _______________ checks of the Medical Air Moisture
,NFPA 99 6040 practice set Questions and
Verified Answers, 100% Score Guarantee
Pass (Latest 2025)
removal system (after cooler, dryer drain, receiver drain,
sight glass, etc.).
A Daily
B Weekly
C Monthly
D Annually - Correct Answers ✅Daily
Per ASSE 6000 Annex D the Medical Air __________ is
typically checked daily.
A Dew Point Monitor
B Carbon Monoxide Monitor
C Filter Condition
D Both A & B
E All of the above - Correct Answers ✅Both A & B
Typical monthly checks, per ASSE 6000 Annex D, of area
alarms include all of the following except :
A Audible Signal
B Visual Signals
C Emergency Instructions
D Gauge Pressure Read Outs - Correct Answers
✅Emergency Instructions
, NFPA 99 6040 practice set Questions and
Verified Answers, 100% Score Guarantee
Pass (Latest 2025)
Per ASSE 6000 Annex D, the medical air compressor
intake location and filter condition should be checked
_______________.
A Daily
B Weekly
C Quarterly
D Annually - Correct Answers ✅Quarterly
Minimum Maintenance Schedule, per ASSE 6000 Annex D,
should include annual checking of ________________ for
Flow, Pressure/Vacuum, Damage, and Wear.
A All outlets & inlets
B All critical care outlets & inlets
C 50% of all critical care outlets
D Annual testing of outlets & inlets is not recommended -
Correct Answers ✅All critical care outlets & inlets
Per ASSE 6000 Annex D the medical air compressor
_____________________ should be calibrated annually.
A Dew Point & Carbon Monoxide Monitors
B Carbon Monoxide Monitor Only