A 440 volts motor has a full load cutting-edge of 34 amperes. What size disconnecting
method is required? - ANS-40 amperes
The score of disconnecting approach is 115% of complete load contemporary.34 * 1.15 =
39.1 amperes.The closer score is forty amperes.
A non-stop load is load where the most current is predicted to maintain for ............ Hours or
greater. - ANS-three
According to the NEC, fixed outside deicing and snow melting gadget is to be taken into
consideration as a _____ load. - ANS-Continuous
a non-stop load is a load anticipated to hold for three (3) hours or greater.The installation
requirements for fixed outdoor electric deicing and snow melting equipment, fixed outdoor
electric deicing and snow melting gadget shall be taken into consideration a continuous
load.When sizing conductors and overcurrent protection for the constant out of doors system
you ought to take into consideration the device can operate over 3 hours, so it is considered
a non-stop load.
All 15,20 amperes receptacle stores installed in toilets of dwelling gadgets shall constantly
require ........................................... - ANS-Ground fault circuit interceptor
Conductors with _____ marked on the insulation are NOT authorized to be used in a wet
vicinity. - ANS-THHN
conductors with THHN insulation are authorised to be used in dry and damp places only and
conductors with THWN, THHW, and THW insulation are diagnosed to be used in dry and
moist places.
Flexible playing cards might not be used within the following places .......... - ANS-To update
a fixed wiring of a structure
For a three hundred ampere electrical circuit, what's the minimal size copper gadget
grounding conductor as according to NEC? - ANS-four awg
4 AWG is the minimal length wire for a three hundred ampere circuit
For a constructing or shape in which the meter enclosure is adjoining to the carrier
disconnecting manner, it's far authorised to ground the meter enclosure to the _____
conductor at the load facet of the service disconnect if floor-fault safety is not supplied. -
ANS-Grounded
, The meter enclosure to be grounded by using connection on the load aspect of the carrier
disconnect where (1) no ground-fault protection is installed, (2) the meter enclosure is
adjacent to the service disconnecting manner, and (3) the grounded service conductor is not
smaller than the scale detailed
For residing units, GFCI protection is required for all unmarried-segment, one hundred
twenty five-volt, 15- and 20-ampere receptacles set up inside six (6) ft of the top internal
edge of the bowl of sinks positioned in _____.
A. Laundry rooms
b. Bathrooms
c. Garages
d. All of those regions - ANS-All of these areas
irrespective of what the location or room in a dwelling, where the 15- or 20-ampere, 125-volt
eceptacles are established inside six (6) feet from the pinnacle inner edge of the bowl of the
sink, GFCI safety ought to be furnished to prevent a ground-fault surprise chance.
For stationary small vehicles rated much less than .................., the branch circuit over
current tool may also function a controller. - ANS-1/ 8 horse energy
Generally, in a movie theater the guide switch for controlling the emergency lighting systems
is permitted to be located _____. - ANS-in an on hand region inside the lobby
observe buildings used as a theater or for a similar cause. Section 520.8 mandates the
manipulate of emergency systems in theaters to conform with the policies set forth in Article
seven hundred; Part V of Article seven hundred applies to the control of emergency lighting
fixtures circuits. Section seven-hundred.21 does no longer allow a manual control switch for
emergency lights to be located in a motion image projection sales space or on a level or
platform; the switch will be located inside the foyer or at a handy handy place.Emergency
lighting systems are designed and established to hold a particular diploma of illumination for
method of egress of the building within the occasion of fire, or comparable emergency, or if
the regular power deliver fails.
Given: A one-circle of relatives residing unit with a call for load of 200 amperes is provided
with a 120/240 volt, single-section, electrical system from the neighborhood utility business
enterprise. What is the MINIMUM size aluminum THW conductors required for use as
service-front conductors for this house? - ANS-four/zero AWG
one-circle of relatives residing 120/240 volt, single-phase, provider-front conductors to be
sized at an ampacity of no longer less than 83% of the service rating. Therefore, two
hundred amperes x 83% = 166 amperes; length 4/0 AWG THW aluminum conductors with
an allowable ampacity of a hundred and eighty amperes must be decided on for this living.
If a 230 volts load is attached to 240 volts energy source, what's the minimum voltage that
may be furnished to load as recommended through NEC? - ANS-228 volts