Fire protection The room must have a sprinkler
for a new system and complete smoke
construction detection OR sprinkler system with
sleeping suite QRS or residential sprinklers
not exceeding
7500 sqft
Fire protection The room mush have direct
for a new supervision AND total coverage
construction automatic smoke detection and
sleeping suite sprinkler system protection with
greater than QRS or residential sprinkler
7500 sqft
,Fire protection The room must have automatic
for existing smoke detection
construction not
exceeding 5000
sqft.
Fire protection Additional fire protection - Sprinkler
for existing protection and smoke partitions.
construction up
to 10,000 sqft
Fire protection The facility must have either quick
for a non response sprinklers or completed
sleeping suite up smoke detection
to 12,500 sqft
Fire protection The facility must have BOTH quick
for a non response sprinklers and complete
sleeping suite up smoke detection
to 15,000 sqft.
Where can you They can be stored in a smoke zone
store up to 300 without seperation.
cubic feet of
medical gas (12
E Cylinders)
,Fire protection It is permitted in a non rated room
for a medical with sprinkler protection and
gas storage clearance from combustibles
room with 300
cubic feet to
3000 cubic feet
worth of Medical
Gas
Fire protection Permitted in 1 hour FRR enclosure
for a medical with vents
gas storage
room with
greater than
3000 cubic feet
worth of Medical
Gas
A hospital and a 2 hour FRR
business
occupancy can
be separated by
this FRR
, A ambulatory 1 hour FRR
care facility and
a business
occupancy can
be separated by
this FRR
How far can a 100 feet
space be in a (Please note that it has to be
room from a exit 150/200 feet from the actual exit or
corridor smoke door)
How far can a 200 feet if sprinklered
space be in a 150 feet if non sprinklered
room from a exit
or smoke
compartment
door.
What FRR does 1 hour FRR
linen and waste
collection rooms
required in
Hospitals
ACTUAL Exam Questions and
CORRECT Answers
Save
Terms in this set (718)
Fire protection The room must have a sprinkler
for a new system and complete smoke
construction detection OR sprinkler system with
sleeping suite QRS or residential sprinklers
not exceeding
7500 sqft
Fire protection The room mush have direct
for a new supervision AND total coverage
construction automatic smoke detection and
sleeping suite sprinkler system protection with
greater than QRS or residential sprinkler
7500 sqft
,Fire protection The room must have automatic
for existing smoke detection
construction not
exceeding 5000
sqft.
Fire protection Additional fire protection - Sprinkler
for existing protection and smoke partitions.
construction up
to 10,000 sqft
Fire protection The facility must have either quick
for a non response sprinklers or completed
sleeping suite up smoke detection
to 12,500 sqft
Fire protection The facility must have BOTH quick
for a non response sprinklers and complete
sleeping suite up smoke detection
to 15,000 sqft.
Where can you They can be stored in a smoke zone
store up to 300 without seperation.
cubic feet of
medical gas (12
E Cylinders)
,Fire protection It is permitted in a non rated room
for a medical with sprinkler protection and
gas storage clearance from combustibles
room with 300
cubic feet to
3000 cubic feet
worth of Medical
Gas
Fire protection Permitted in 1 hour FRR enclosure
for a medical with vents
gas storage
room with
greater than
3000 cubic feet
worth of Medical
Gas
A hospital and a 2 hour FRR
business
occupancy can
be separated by
this FRR
, A ambulatory 1 hour FRR
care facility and
a business
occupancy can
be separated by
this FRR
How far can a 100 feet
space be in a (Please note that it has to be
room from a exit 150/200 feet from the actual exit or
corridor smoke door)
How far can a 200 feet if sprinklered
space be in a 150 feet if non sprinklered
room from a exit
or smoke
compartment
door.
What FRR does 1 hour FRR
linen and waste
collection rooms
required in
Hospitals