The regulations to enforce compliance of underground storage tank systems in the state are
found in?

a.) Code of Federal Regulations, 40 CFR Part 281
b.) California Code of Regulations, Title 23, Chapter 16
c.) Code of Federal Regulations, 40 CFR Part 280
d.) California Code of Regulations, Title 23, Chapter 17 - ANSWER>>b.) California Code of
Regulations; Title 23, Chapter 16

By definition an "underground storage tank system" includes

a.) The tank, all connected piping and dispensers
b.) The tank, all connected piping, ancillary equipment and containment system
c.) Only the tank
d.) Only tanks totally beneath the surface of the ground - ANSWER>>b.) The tank, all connected
piping, ancillary equipment and containment system

(H&SC, Sec 25281(z))

Under-dispenser containment was required for all UST systems by ___________.

a.) December 31, 2003
b.) July 1, 1987
c.) January 1, 1984
d.) January 1, 2000 - ANSWER>>a.) December 31, 2003

CCR Title 23, Sec 2636(g)(C)

According to California Law, UST systems installed after July 1, 2003, require a one-time ELD
test to ensure that the tank is product tight...

a.) If the tank is located within one (1) mile of a public drinking water well

,b.) If the tank is located within 1000 feet of a public drinking water well
c.) Unless the tank is equipped with secondary containment
d.) In all cases - ANSWER>>For ALL tanks before use (H&SC 25290.2 (I))
d.) In all cases

H&SC, Sec 25290.2(i)

The written report submitted to the local agency after an unauthorized release is required to
include the following except:

a.) Description of actions taken to stop the release
b.) Cause of the release
c.) Method of disposal of released product
d.) Date on which the release was discovered - ANSWER>>b.) Cause of the release

CCR Title 23, Sec 2652(c)

An unauthorized release which does not escape from secondary containment only requires a
record on the operator's monitoring reports provided:

A. It did not increase the hazard of fire
B. It did not cause any deterioration of the secondary containment
C. It was cleaned up within 8 hours of detection
D. All of the above - ANSWER>>D. All of the above

H&SC, Sec 25294

The annual monitoring certification may be performed by:

A. A person possessing the appropriate contractors licenses
B. An individual trained and certified by the manufacturer of the monitoring equipment
C. A designated UST operator
D. A person who meets the requirements of both a and b - ANSWER>>D. A person who meets
the requirements of both a and b

CCR Title 23, Sec 2715(i)

The following is true of secondary containment testing, EXCEPT:

,a.) Must be tested every 24 months
b.) Must be tested every 36 months
c.) Results must be submitted to the local agency within 30 days of testing
d.) Local agency must be notified 48 hours prior to testing - ANSWER>>a.) Must be tested every
24 months

CCR Title 23, Sec 2637(a)

Records of cathodic protection system maintenance must be kept on file for ______________.

a.) 10 years
b.) 1.5 years
c.) 3 years
d.) 6.5 years - ANSWER>>d.) 6.5 years

CCR Title 23, Sec 2712(b)

Impressed current cathodic protection systems shall be inspected no less than every
___________ to ensure that they are in proper working order:

a.) 60 days
b.) 90 days
c.) 30 days
d.) 120 days - ANSWER>>a.) 60 days

CCR Title 23, Sec 2635(a)(2)

Monthly monitoring data must be kept on file for _________________.

a.) 3 years
b.) 6.5 years
c.) 5 years
d.) For the life of the UST system - ANSWER>>a.) 3 years

CCR Title 23, Sec 2712(b)

, By December 22, 1998, all automatic line leak detectors installed on single-walled pressurized
piping must be capable of:

a.) Restricting product flow
b.) Triggering an audible and visual alarm
c.) Shutting down the pumping system
d.) Shutting off the flow at the dispenser - ANSWER>>c.) Shutting down the pumping system

CCR Title 23, Sec 2666(c)

When an automatic tank gauge is utilized for single-walled tank leak detection, it shall generate
a post-test hard copy data report of the following information, except:

a.) Liquid volume
b.) Fuel depth
c.) Outside air temperature
d.) Time and date of test - ANSWER>>c.) Outside air temperature

CCR Title 23, Sec 2643(b)(1)

If a UST system is utilizing an overfill alarm, the alarm must be triggered to alert the transfer
operator when the tank is no more than ___________ full

a.) 85%
b.) 95%
c.) 90%
d.) 80% - ANSWER>>c.) 90%

CCR Title 23, Sec 2635(b)(2)(A)

A service technician has performed calibration and maintenance on an ATG probe; this
maintenance record must be kept on file for ______________.

a.) 6.5 years
b.) 3 years
c.) 5 years
d.) Life of the UST system - ANSWER>>c.) 5 years

Document information

Uploaded on
April 26, 2025
Number of pages
47
Written in
2024/2025
Type
Exam (elaborations)
Contains
Questions & answers
$15.49

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
AndrewBenson
3.0
(2)
Sold
29
Followers
0
Items
2169
Last sold
5 days ago



Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions