4 - correct answer✔️✔️Consider a room which is 40' square. How many 15cd wall
mounted strobes are required to adequately cover this space?
Annually - correct answer✔️✔️What is the testing frequency of a strobe?
15 - correct answer✔️✔️In a corridor application, visible appliances shall be rated
not less than ________ cd?
4 hours - correct answer✔️✔C ️ onsider a household fire alarm system where the
primary power is provided by a circuit that can be switched off by means other
than a circuit breaker. The battery must be recharged in____________
The control unit shall identify the affected detector when the compensation limit
has been reached. - correct answer✔️✔W ️ here automatic drift compensation of
detectors is provided:
3 - correct answer✔️✔️A fire alarm system requires the use of smoke detectors
in a corridor. The corridor is 10' wide and 120' long. The ceiling of the corridor is
smooth and flat and 10' high. What is the minimum number of smoke detectors in
the corridor.
SUCCESS
, STUDYSAGE
One half smooth ceiling
NFPA 72 17.7.3.2.4.2(2)bi pg 98 - correct answer✔️✔️The fire alarm system
design for a room called for smoke detector spacing based on a smooth flat
ceiling. Upon inspecting the room, it is determined that the ceiling has beams.
The beam spacing is less than 40% of the ceiling height. NFPA72 permits smooth
ceiling spacing in the direction parallel to the beams and __________ spacing in
the direction perpendicular to the beams.
3 - correct answer✔️✔️The working drawings for a fire alarm system show that 2
duct detectors are required. The building is a single story with 4 HVAC units (1-
5,000 cfm, 1-4000 cfm, 1-3000 cfm, 1-2000 cfm) How many duct detectors are
required?
15
NFPA72 18.4.3.1 pg107 - correct answer✔️✔️The fire alarm system for a building
requires the use of audible notification appliances for public mode notification. To
ensure public mode signals are clearly heard, they shall have a sound level of at
least _______ db above the average ambient sound level?
Location of utilities - correct answer✔️✔️Site plans typically include:
Level - correct answer✔️✔️A ceiling surface has a slope of 1 in 9. This is
considered a ____________ ceiling.
Division 16-Electrical - correct answer✔️✔W ️ hich section of the contract
documents typically contain fire alarm system requirements?
9