July 1 2005, service techs shall possess or work under someone who has a
current certification indicating he or she has passed the ? - ✔✔California UST
service technician exam
ICC cert must be renewed every? - ✔✔24 months
Service techs must posses or be employed by a person who has the appropriate
contractors license unless? - ✔✔The individual has a Tank testing licens
Service tech is defined by any individual who? - ✔✔Test UST monitoring
equipment
Trouble shoots UST systems
Installs UST monitoring equipment
If the manufacturer training no longer exist , the local angency may? -
✔✔Approve comparable alternat training .
UST includes? - ✔✔Tank and connected piping
What is considered and UST - ✔✔petroleum storage tank
What UST system meets the requirements for secondary containment? -
✔✔Doubled wall tanks
1|Page
©KERRYMARTIN 2025/2026. YEAR PUBLISHED 2025.
, According to title 23; the following piping components if installed after July 1
1987 must have secondary containment - ✔✔Pressured product piping
Considered "pipe" on tanks installed after July 1 2003 - ✔✔Pressured product
piping and below ground vapor recovery
Under dispenser containment (UDC) was required for all UST systems by -
✔✔December 31 2003
System for exchanging gas vapors in a storage tank and product in a fuel
delivery truck - ✔✔Stage 1 vapor recovery
An approved method for non visual monitoring for existing UST systems. -
✔✔Statistical Inventory Reconciliation (SIR)
ATG must be capable for detecting a release of ? - ✔✔.2 gallons per hour
Manual inventory reconciliation. - ✔✔No longer an approved method for non
visual monitoring on existing UST systems
Automatic line leak detectors installed on underground piping with secondary
containment shall be capable of tetecting a leak of ? - ✔✔3 gallons per hour at
10 psi
ATG should be programmed to test the tank ? - ✔✔At least monthly