DETERMINE QUALIFICATIONS. - Answer -✔✔OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES
FOR A MIN. OF __________ YEARS. - Answer -✔✔3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. - Answer -✔✔IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - Answer -
✔✔1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - Answer -✔✔1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED
TO SERVICE WITHIN ______ HOURS. - Answer -✔✔8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. -
Answer -✔✔OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - Answer -✔✔30
WHAT DOES "OOS" STAND FOR? - Answer -✔✔OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - Answer
-✔✔TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND
ANY SECTIONAL VALVES. - Answer -✔✔MASTER FIRE SUPPRESSION PIPING
CONTRACTOR
,__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND
FLOW PRESSURES BEFORE AND AFTER. - Answer -✔✔DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________. - Answer -✔✔NO IMPAIRMENT WAS
FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - Answer -✔✔MAIN
CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________
TAG PLACED ON THE MAIN CONTROL VALVE. - Answer -✔✔RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - Answer -✔✔WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE. - Answer -✔✔BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER,
CENTRAL STATION AND OCCUPANTS. - Answer -✔✔INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE
THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - Answer -
✔✔IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT
GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM
FREEZING. - Answer -✔✔50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR
THE ____________. - Answer -✔✔MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE
FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - Answer -
✔✔RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND
COURT PROCEEDINGS. - Answer -✔✔REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY
HOLD THE FOLLOWING CERTS: - Answer -✔✔REFRIGERATION OPERATING
ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH
PRESSURE OPERATING ENGINEER.
, A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE
AND SPRINKLER SYSTEMS. - Answer -✔✔MASTER FIRE SUPPRESSION PIPING
CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS. - Answer -✔✔30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED
WHEN SPRINKLERS ARE INSTALLED. - Answer -✔✔96
WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO
PREVENT THE SYSTEM FROM FREEZING. - Answer -✔✔40 FAHRENHEIT
__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED. - Answer -
✔✔COLD WEATHER
________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE
HEATED TO PREVENT FREEZING. - Answer -✔✔DRY PIPE
THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE TO OPEN. - Answer
-✔✔AIR PRESSURE
IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS) THE
ALARM IS TRANSMITTED DIRECTLY TO THE _________. - Answer -✔✔FIRE
DEPARTMENT
DRY PIPE VALVES ARE OF A ______ DESIGN. - Answer -✔✔CLAPPER
DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE NORMAL
TRIP LEVEL. - Answer -✔✔15-20
AN ACCELERATOR AND EXHAUSTER ARE USED TO _______THE TIME TO
ALLOW WATER INTO THE SYSTEM. - Answer -✔✔REDUCE
BOTH ACCLERATOR AND EXHAUSTER ARE ACTIVATED WHEN A DROP OF
_______ PSI IS DETECTED IN THE SYSTEM. - Answer -✔✔2
IN A PREACTION SYSTEM, THE ___________ IS OPENED BEFORE THE
SPRINKLER HEADS. - Answer -✔✔PREACTION VALVE
PREACTION SYSTEM ALARMS ARE GIVEN AS SOON AS THE _________ IS
OPENED. - Answer -✔✔VALVE