Sprinkler test Question And Correct Solutions Class 1 commodity is more combustible then class 3 - Answer -False All holes for lag screws shall be pre-drilled __________ inch less in diameter than the max. root diameter of the lag screw thread. - Answer -1/8in Coach screws shall not be used for support of pipes larger than ________ inch in diameter. - Answer -4 Distance between supports on a riser shall not exceed _________ feet. - Answer -25ft Fire department connections shall be installed so that they are located not less than ______ nor more than ______ above the level of the adjoining ground, sidewalk, or grade surface. - Answer -18in , 48in Flexible couplings shall be installed on risers within_____ inches above and _____ inches below the floor in multi-story buildings. - Answer -12in and 24in For ESFR sprinklers, the clearance between the deflector and the top of storage shall be ____ inches or greater - Answer -36in For extra hazard occupancies, the maximum distance between sprinklers shall not exceed ______ feet - Answer -12ft Hangers shall be designed to support _______ times the weight of water-filled pipe plus ________ at each point of piping support. - Answer -5 and 250 Hose connections and hose stations shall be unobstructed and shall be located not less than ______ nor more than ______ above the floor. Answers - Answer -36in, 60in How high can storage be before it is considered high-piled storage? - Answer -12ft How shall the sprinkler head protecting the dry pipe valve enclosure be fed? - Answer -From the dry side of the system In residential applications, fire department connections are required to be a minimum of _______ in size. - Answer -1 1/2" Is the use of reconditioned valves and devices as replacement equipment in existing systems allowed? - Answer -Yes Joints for the connection of copper pipe an fittings on dry and preaction systems shall be brazed. - Answer -True Lateral sway bracing shall be spaced at a minimum of __________ feet on center on all feed and cross mains regardless of size and on all piping 2 1/2" and larger - Answer -40ft Lateral sway bracing shall not apply to pipes individually supported by rods less than ______ inches long measured between the top of the pipe and the point of attachment to the building structure. - Answer -6in Longitudinal sway bracing spaced at a maximum of ________ feet on center shall be provided for feed and cross mains. - Answer -80ft No clearance is required if flexible couplings are located within _____ each side of a wall, floor, platform, or foundation. - Answer -12in Ordinary hazard occupancy protection areas shall not exceed ________ square feet. - Answer -130 Pressure tanks should be kept ________ full of water. - Answer -2/3 Pressure tanks should maintain an air pressure of at least ______ psi. - Answer -75PSI Risers shall be supported by pipe clamps or by hangers located on the horizontal connections within ________ inches of the centerline of the riser. - Answer -24in Screwed unions shall not be used on pipe larger than _________ inch - Answer -2in

Content preview

THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. - Answer -✔✔OWNER

RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES
FOR A MIN. OF __________ YEARS. - Answer -✔✔3

THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. - Answer -✔✔IMPAIRMENT COORDINATOR

REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - Answer -
✔✔1

SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - Answer -✔✔1

NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED
TO SERVICE WITHIN ______ HOURS. - Answer -✔✔8

FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. -
Answer -✔✔OWNER OF THE BUILDING

IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - Answer -✔✔30

WHAT DOES "OOS" STAND FOR? - Answer -✔✔OUT OF SERVICE

OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - Answer
-✔✔TAGS

A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND
ANY SECTIONAL VALVES. - Answer -✔✔MASTER FIRE SUPPRESSION PIPING
CONTRACTOR

,__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND
FLOW PRESSURES BEFORE AND AFTER. - Answer -✔✔DRAIN TEST RESULTS

GREEN TAGS INDICATE THAT __________. - Answer -✔✔NO IMPAIRMENT WAS
FOUND

GREEN TAGS WILL BE PLACED ON THE ____________. - Answer -✔✔MAIN
CONTROL VALVE

SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________
TAG PLACED ON THE MAIN CONTROL VALVE. - Answer -✔✔RED

A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - Answer -✔✔WHITE

A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE. - Answer -✔✔BLUE

THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER,
CENTRAL STATION AND OCCUPANTS. - Answer -✔✔INSURANCE

PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE
THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - Answer -
✔✔IMPAIRMENT COORDINATOR

GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT
GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM
FREEZING. - Answer -✔✔50, 40

THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR
THE ____________. - Answer -✔✔MAIN CONTROL VALVE

__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE
FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - Answer -
✔✔RECORDS

FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND
COURT PROCEEDINGS. - Answer -✔✔REVOCATION

THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY
HOLD THE FOLLOWING CERTS: - Answer -✔✔REFRIGERATION OPERATING
ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH
PRESSURE OPERATING ENGINEER.

, A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE
AND SPRINKLER SYSTEMS. - Answer -✔✔MASTER FIRE SUPPRESSION PIPING
CONTRACTOR (MFSPC)

A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS. - Answer -✔✔30

ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED
WHEN SPRINKLERS ARE INSTALLED. - Answer -✔✔96

WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO
PREVENT THE SYSTEM FROM FREEZING. - Answer -✔✔40 FAHRENHEIT

__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED. - Answer -
✔✔COLD WEATHER

________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE
HEATED TO PREVENT FREEZING. - Answer -✔✔DRY PIPE

THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE TO OPEN. - Answer
-✔✔AIR PRESSURE

IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS) THE
ALARM IS TRANSMITTED DIRECTLY TO THE _________. - Answer -✔✔FIRE
DEPARTMENT

DRY PIPE VALVES ARE OF A ______ DESIGN. - Answer -✔✔CLAPPER

DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE NORMAL
TRIP LEVEL. - Answer -✔✔15-20

AN ACCELERATOR AND EXHAUSTER ARE USED TO _______THE TIME TO
ALLOW WATER INTO THE SYSTEM. - Answer -✔✔REDUCE

BOTH ACCLERATOR AND EXHAUSTER ARE ACTIVATED WHEN A DROP OF
_______ PSI IS DETECTED IN THE SYSTEM. - Answer -✔✔2

IN A PREACTION SYSTEM, THE ___________ IS OPENED BEFORE THE
SPRINKLER HEADS. - Answer -✔✔PREACTION VALVE

PREACTION SYSTEM ALARMS ARE GIVEN AS SOON AS THE _________ IS
OPENED. - Answer -✔✔VALVE

Document information

Uploaded on
January 14, 2025
Number of pages
17
Written in
2024/2025
Type
Exam (elaborations)
Contains
Questions & answers
$11.69

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Sold
0
Followers
0
Items
88
Last sold
-



Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions