rises or falls over 3 inches (NFPA 72, Table 14.4.3.2 17 (j) (4) - Answer-When testing a water level
supervisory switch serving a pressure tank a signal shall indicate if the water level _____________from
the required level
the visible appliance (Nfpa 72 18.4.8.1) - Answer-If combination audible/visible appliances are installed
the location of the installed appliance shall be determined by the requirements of
26 (Nec Annex C tables) - Answer-What is the maximum number of 12 gauge THHN wires that can be
installed in 1" EMT
150 Ohms - Answer-Two resistors are connected in parallel. R1 = 300 Ohms, R2 = 300 Ohms. What is
their equivalent resistance?
12 - Answer-A Room is 200' long and 150' wide and the 8' high ceiling is smooth and flat. A spot type
heat detector has been selected that is listed for a 30' maximum spacing between detectors. According
to NFPA 72 how many detectors will be needed to protect this room?
rises or falls over 3 inches (NFPA 72, Table 14.4.3.2 17 (j) (4) - Answer-When testing a water level
supervisory switch serving a pressure tank a signal shall indicate if the water level _____________from
the required level
the visible appliance (Nfpa 72 18.4.8.1) - Answer-If combination audible/visible appliances are installed
the location of the installed appliance shall be determined by the requirements of
26 (Nec Annex C tables) - Answer-What is the maximum number of 12 gauge THHN wires that can be
installed in 1" EMT
150 Ohms - Answer-Two resistors are connected in parallel. R1 = 300 Ohms, R2 = 300 Ohms. What is
their equivalent resistance?
12 - Answer-A Room is 200' long and 150' wide and the 8' high ceiling is smooth and flat. A spot type
heat detector has been selected that is listed for a 30' maximum spacing between detectors. According
to NFPA 72 how many detectors will be needed to protect this room?