NICET LEVEL 1 TEST QUESTIONS AND
ANSWERS
4 wires - Answer-what is the maximum number of 14 AWG RHH conductors which can be installed in
1/2 rigid metal conduit?
3.5'-48" to the actuator - Answer-Which of the following would be an appropriate mounting height for a
pull station?
1 flash per second - Answer-What is the minimum flash rate for a visible notification device?
90" to the top of the device - Answer-What is the minimum mounting height for audible notification
devices?
Such that the entire lens is not less then 80" - Answer-What is the minimum mounting height for visible
notification devices?
Voltage=Current X Resistence - Answer-What is the formula for Ohm's Law
, Put your meter in series with the circuit - Answer-When using your mult-meter to measure, you must:
Semi-annually - Answer-Waterflow devices shall be tested with that frequency?
Annually - Answer-With what frequency shall ionization smoke detectors be given a functional test?
24 hours in normal operation, 5 minutes in alarm - Answer-What are the standby power requirements
for a proprietary signaling system?
Shunt type - Answer-Which of the following is a type of auxiliary protective signaling system?
A UL listed central station
A receiver located at an unlisted monitoring facility
A fire department or communications center - Answer-Remote station signaling systems are permitted
to send signals to:
600V - Answer-Non-power limited fire alarm cable shall have an insulation rating of:
20,000 CFM HVAC system serving a single floor
15,000 CFM HVAC system serving 3 floors
20,000 CFM HVAC system serving 2 floors - Answer-Which of these HVAC systems would require duct
detectors on supply and return?
Group A, E, F - Answer-According to the IBC, which of the following use Groups require visual
notification?
ANSWERS
4 wires - Answer-what is the maximum number of 14 AWG RHH conductors which can be installed in
1/2 rigid metal conduit?
3.5'-48" to the actuator - Answer-Which of the following would be an appropriate mounting height for a
pull station?
1 flash per second - Answer-What is the minimum flash rate for a visible notification device?
90" to the top of the device - Answer-What is the minimum mounting height for audible notification
devices?
Such that the entire lens is not less then 80" - Answer-What is the minimum mounting height for visible
notification devices?
Voltage=Current X Resistence - Answer-What is the formula for Ohm's Law
, Put your meter in series with the circuit - Answer-When using your mult-meter to measure, you must:
Semi-annually - Answer-Waterflow devices shall be tested with that frequency?
Annually - Answer-With what frequency shall ionization smoke detectors be given a functional test?
24 hours in normal operation, 5 minutes in alarm - Answer-What are the standby power requirements
for a proprietary signaling system?
Shunt type - Answer-Which of the following is a type of auxiliary protective signaling system?
A UL listed central station
A receiver located at an unlisted monitoring facility
A fire department or communications center - Answer-Remote station signaling systems are permitted
to send signals to:
600V - Answer-Non-power limited fire alarm cable shall have an insulation rating of:
20,000 CFM HVAC system serving a single floor
15,000 CFM HVAC system serving 3 floors
20,000 CFM HVAC system serving 2 floors - Answer-Which of these HVAC systems would require duct
detectors on supply and return?
Group A, E, F - Answer-According to the IBC, which of the following use Groups require visual
notification?