TESTER (BPAT) EXAM LATEST 2025
ACTUAL EXAM COMPLETE QUESTIONS
AND CORRECT DETAILED ANSWERS
(VERIFIED ANSWERS) |ALREADY GRADED
A+
If not marked, a pressure vacuum breaker's critical level is ____?
A. At the bottom of the valve body
B. Measured from the check valve inlet
C. Measured from the body outlet
D. Not important
E. The air-inlet valve opening Correct Answer At the bottom of
the valve body
A pressure vacuum breaker may have ____ on the assembly's
discharge piping.
A. Auxiliary water supply looped irrigation
B. A boiler
C. A booster pump
D. Elevated piping
E. Irrigation sprinkler heads Correct Answer Irrigation sprinkler
heads
The minimum loading to open a pressure vacuum breaker's air-
inlet valve is ____?
A. 1 psi (6.89 kPa)
B. 2 psi (13.8 kPa)
C. 3 psi (20.7 kPa)
D. 4 psi (27.6 kPa)
,E. 5psi (34.5 kPa) Correct Answer 1 psi (6.89 kPa)
The recorded value of a pressure vacuum breaker check valve is
determined when ____?
A. Both shut-off valves are closed
B. The high-bleed valve is opened
C. The air-inlet valve opens
D. Water stops flowing from test cock 1
E. Water stops flowing from test cock 2 Correct Answer Water
stops flowing from test cock 2
Pressure vacuum breaker shut-off valves must be _____ valves.
A. Angle
B. Gate
C. Globe
D. Regulating
E. Tightly closed Correct Answer Tightly closed
An indication that a pressure vacuum breaker is undersized for its
application is _____?
A. Air-inlet valve leakage
B. Bonnet distortion
C. Chatter or noise during flow
D. Disc pitting
E. Spring elongation Correct Answer Chatter or noise during flow
Continuous flow from a pressure vacuum breaker's test cock 2
with shut-off valve 2 open and shut-off valve 1 closed is an
indication of _____?
A. Backpressure backflow
B. Backsiphonage backflow
C. A failed air-inlet valve
D. A leaking check valve
E. A leaking or damaged shut-off valve 1 Correct Answer
Backpressure backflow
, Pressure vacuum breakers may be used on the following
applications except ____?
A. High hazard/backsiphonage
B. High hazard/continuous pressure
C. Low hazard/backpressure
D. Low hazard/backsiphonage
E. Low hazard/intermittent pressure Correct Answer Low
hazard/backpressure
A double check valve assembly is installed 12 in. (30.5 cm) above
the floor for _____?
A. Electrical code compliance
B. Floor draining
C. Maintenance
D. Mechanical code compliance
E. Rodent control Correct Answer Maintenance
Double check valve assembly product performance standards
require venting for _____?
A. Chemicals
B. Test cock corrosion
C. Trapped air
D. Vertical installations
E. Winterization Correct Answer Trapped air
A low-hazard use only backflow preventer is a(n) _____?
A. Air-gap separation
B. Atmospheric vacuum breaker
C. Double check valve assembly
D. Pressure vacuum breaker assembly
E. Reduced pressure principle assembly Correct Answer Double
check valve assembly