A hospital is adding two additions onto a building:
1) an outpatient imaging center classified as ambulatory Healthcare Occupancy
2) A retail space and physicians offices classified as Business Occupancy
What fie separations are required? - CORRECT ANSWER ✔✔ -The hospital must be separated
from the other occupancies by a 2 Hr fire separation (NFPA 101, 18.1.3.3 & 19.1.3.3)
For a health care organization that uses accrediting agencies, who designates the person
responsible for managing survey related deficiencies? - CORRECT ANSWER ✔✔ -The health
care organization
How often should storage batteries associated with a Level 1 or Level 2 EPSS (Emergency
Power Supply System) be inspected as required by NFPA 110? - CORRECT ANSWER ✔✔ -
Storage batteries associated with Level 1 & Level 2 EPSS should be inspected weekly (NFPA
110, 8.3.7)
Is the Jockey Pump Run Status required to be monitored by the Fire Alarm Master Control
Station? - CORRECT ANSWER ✔✔ -No, the Jockey Pump runs as needed to ensure system
design pressure is kept within normal conditions