Arc-Flash Basics
What is an arc-flash hazard?
According to the National Fire Protection Association (NFPA) 70E: Standard for Electrical Safety in the
Workplace, an arc-lash hazard is “a source of possible injury or damage to health associated with the
release of energy caused by an electrical arc.” In an arc-lash event, a lashover of electric current
leaves its intended path and travels through the air from one conductor to another or to ground. During
such an event, the air gets suficiently heated to become ionized; the air becomes the conductor.
Arc-lash events can cause dangerous and potentially fatal heat, ultraviolet radiation, blast pressure, and
lying shrapnel along with deafening sound waves. The resulting release of arc-lash energy, referred to
as “incident energy,” is a measure of thermal energy at a working distance from an arc fault.
What causes an arc flash?
Arc-lash events can be caused by numerous factors, such as the shorting of two phases, which creates
a phase-to-phase fault. Common causes of phase-to-phase faults include dropped tools, accidental
contact by maintenance personnel, the buildup of corrosion or conductive dust on conductors, and the
presence of pests, like mice, rats, or snakes, that come in contact with energized conductors.
What elements must be present for an arc-flash event to occur?
1.
2.
Air gap from using air as an insulator or from a damaged insulator.
Suficient energy (fault current available from the power source) to initiate and sustain the arc-lash
event. This is normally satisied in low-voltage (480 V and above) and medium-voltage switchgear
environments.
3. Something to trigger the arc lash. This could be a rodent, acting as a conductor across the phase
conductors, or one of the causes listed above.
How does a protective relay help mitigate incident energy from an arc-flash event?
The faster the extinction of the arc-lash event, the smaller the amount of incident energy that is
released. Since arc-lash energy is proportional to voltage multiplied by current multiplied by time
(V•I•t), the protective relay acts to reduce the duration of the arc-lash event, or “t.” In an arc-lash
event, this equals the time elapsed before the relay trips plus the breaker clearing time.
Relays don’t have any control over the voltage and current. The voltage across an arc is determined by
the conductor gap; the arcing current is limited by the available fault current. What the relay can impact
is time. By limiting the duration of the arc-lash event, the relay can dramatically reduce the amount of
incident energy produced by an arc-lash event.
What role do air gaps play in an arc flash?
While air is a good electrical insulator under normal conditions, if the air gets heated up and becomes
ionized, that air will become a conductor, resulting in an arc-lash event. In environments with air gaps,
such as electrical switchgear, arc-lash hazards exist with exposed copper or aluminum conductors; e.g.,
a busbar, contacts on the motor contactor, or breaker contacts.
4
Are there other dangers in an arc-flash event besides intense heat and light?
High-voltage arcs can also produce considerable pressure waves by rapidly heating the air and creating
a blast. This pressure blast can hit a worker with great force and send molten metal droplets from
melted copper and aluminum electrical components great distances at extremely high velocities.
How much light is produced in an arc flash?
In a very small (2,000 A) arc-lash event, the measured light intensity can be 2,000,000 lux, or twenty
times brighter than bright sunlight, at a distance of 1 meter from the arc-lash source. For more realistic
arcing currents (e.g., 17,000 A), we have recorded arc-lash light intensities of 12,000,000 lux. This is
equivalent to the amount of light generated by 120 suns in the sky at
Content preview
SEL Arc-Flash Detection (AFD)
Questions and Answers
, Contents
Arc-Flash Basics
What is an arc-flash hazard? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
What causes an arc flash? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
What elements must be present for an arc-flash event to occur? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
How does a protective relay help mitigate incident energy from an arc-flash event? . . . . . . . . . . . . . . 4
What role do air gaps play in an arc flash? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Are there other dangers in an arc-flash event besides intense heat and light? . . . . . . . . . . . . . . . . . . . 5
How much light is produced in an arc flash? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
How is the current determined in an arc-flash event?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Solutions Overview
How does SEL arc-flash technology mitigate arc-flash hazards? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
How does SEL sensor-based AFD technology work? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Which products represent the SEL family of sensor-based AFD products? . . . . . . . . . . . . . . . . . . . . . . . 6
Configuration
How is arc-flash mitigation configured with SEL protective relays? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
What is the maximum number of arc-flash sensors I can connect to an SEL relay?. . . . . . . . . . . . . . . . 6
Light Sensors
Why do I need light sensors? Isn’t the overcurrent element in a protective relay sufficient to
sense when an arc-flash event occurs? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
How does the SEL light-sensing technology work? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
How do I know that the arc-flash-sensing technology will continue to work over time?
Do I test the sensors periodically to verify that they’re working? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
How do I test the arc-flash sensors during commissioning to verify that they’re in
working order? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
When should I use the bare-fiber sensor vs. the point sensor? Can I mix and match them
on the same relay? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Has there ever been an arc-flash event where the arc-flash sensors were destroyed
before they signaled the relay?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Does SEL sell or provide the necessary tools to cut and install arc-flash fiber-optic cabling?. . . . . . . 8
Installation
Where do you recommend placing the arc-flash sensors in the compartment? . . . . . . . . . . . . . . . . . . . 8
Are SEL light sensors vulnerable to dust?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
How does SEL recommend adjusting the sensitivity of the sensors? . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2