Where supervised automatic sprinkler systems are required by Code, which
standard or code regulates supervisory attachment installation? - Answer: NFPA
72, National Fire Alarm Code
1
, FAL TFM12 BFAT3
A colorless, odorless, electrically non-conductive inert gas that extinguishes fire
and forms dry ice snow when released directly into the atmosphere - Answer:
Carbon dioxide gas
An automatic smoke detector that requires continuous presence of smoke above
the alarm threshold for more than 1 minute before initiating an alarm is said to
equipped with which feature below? - Answer: Alarm Verification
Fire Alarm conductors in Class 1, Division 1 locations shall be - Answer: Multi or
single conductor Copper in IMC or GRC
The following wiring methods are not permitted for Fire Alarm conductors
installed in Class 1 Division 2 locations - Answer: none of the above, all are
acceptable methods
Fire Alarm equipment shall be durably marked where plainly visible to indicate
each circuit - Answer: That is is Power-limited fire alarm circuit
Smoke detectors listed for use in air distribution systems moving more that
2000ft3/min shall be located - Answer: on the supply air side downstream of the
air filters
For smooth ceiling coverage, all points on the ceiling are required to have a
detector within a distance of - Answer: 70% of the selected spacing