NICET Level 1 inspection and Testing | 75 Questions with 100% Correct Answers | Verified | Latest Update 2024
When using a pulse load tester on a sealed lead acid battery, the minimum acceptable capacity is... - 80% When a software change is made to a fire alarm system, what percentage of the initiating devices not affected by the change must be tested - 10% When testing elevator recall, the elevator should go to the alternate level when: - The lobby smoke detector on the recall level is activated Minimum requirement for system documentation - Battery calculations/floor plan/sequence of operations/voltage drop calculations Carbon monoxide detectors used for the toxicity of gas fired heating equipment must be tested annually per NFPA 72 - False What is the maximum time period to replace a lead acid battery - Per manufacturers recommendation What type of instrument is normally used to test the specific gravity of lead acid battery cells - Hydrometer