rated A+ already answered 2023
Corrosion Specialist - correct answer designs and certifies cathodic protection system
Secondary containment shall be constructed to contain at least the following volumes: - correct answer
A. 100% of usable capacity of primary where there is only one primary is within the secondary
B. 150% of the largest container if there are multiple primary containers in a single secondary
Cathodic protection tester will test cathodic protection system within __ months of installation and every
__ years thereafter - correct answer 6 months
3 years
Spill container shall meet the following requirements: - correct answer A. If made of metal, exterior wall
shall be protected from galvanic corrosion
B. Shall have minimum capacity of 5 gallons (19 L)
C. Shall have drain valve which allows drainage of the collected spill into the primary container or
provide means to keep spill cont empty
Overfill prevention shall alert transfer operator when tank is __% full - correct answer 90%
Flapper Valves shall provide positive shut off when tank is filled to no more than __% capacity - correct
answer 95%
Primary pressurized piping shall be tested for tightness hydrostatically at __% of design operating
pressure - correct answer 150%
Date that all UST systems must have Line Leak Detector installed - correct answer November 9,2004