REFRIGERATION MECHANIC LICENSING EXAM NEWEST EVALUATED EXAM
PRACTICE 120 QUESTIONS 2026-2027|ORIGINAL QUESTIONS & ANSWERS
|DETAILED RATIONALES |HINTED COMPLETE EXAM PREP GRADED
A+*INSTANT DOWNLOAD PDF*

1. A refrigeration system using R-410A is operating with a suction pressure of 118
psig. What is the approximate saturated evaporator temperature?
A) 10°F
B) 40°F
C) 55°F
D) 20°F
Answer: B - 40°F 118 psig corresponds to approximately 40°F saturation for R-
410A. This is a critical pressure-temperature relationship for checking
evaporator performance.
2. What is the primary purpose of superheat in a refrigeration system?
A) To increase compressor capacity
B) To cool the condenser
C) To ensure only vapor enters the compressor
D) To reduce discharge temperature
Answer: C - To ensure only vapor enters the compressor Superheat prevents
liquid slugging which can severely damage compressor valves and bearings. 8-
12°F is typical at the evaporator outlet.
3. A hermetic compressor is drawing high amperage and tripping on overload
shortly after starting. The most likely cause is?
A) Low refrigerant charge
B) Faulty thermostat
C) Shorted compressor windings or seized compressor
D) Dirty condenser coil
Answer: C - Shorted compressor windings or seized compressor Locked rotor
or shorted windings causes LRA (Locked Rotor Amps) draw, significantly higher
than RLA, tripping the overload protector.
4. According to EPA Section 608, what is the maximum allowable leak rate for
comfort cooling appliances containing 50 lbs or more of refrigerant?
A) 35% per year
B) 10% per year
C) 20% per year

, D) 15% per year
Answer: B - 10% per year EPA defines comfort cooling leak threshold as 10%,
commercial refrigeration 20%, and industrial process 30% for charges of 50 lbs
or more.
5. What does a high superheat reading combined with low suction pressure
indicate?
A) Overcharge
B) Undercharge or restriction in low side
C) Faulty compressor valves
D) Non-condensables in system
Answer: B - Undercharge or restriction in low side Starved evaporator cannot
absorb enough heat, resulting in low suction pressure and the remaining
refrigerant superheats excessively.
6. The function of a TXV (Thermostatic Expansion Valve) is to?
A) Control condenser pressure
B) Maintain constant superheat by regulating refrigerant flow to evaporator
C) Control compressor speed
D) Prevent liquid from entering condenser
Answer: B - Maintain constant superheat by regulating refrigerant flow to
evaporator TXV modulates flow based on bulb temperature and evaporator
pressure to maintain 8-12°F superheat.
7. What type of compressor oil is required for use with HFC refrigerants like R-
134a and R-410A?
A) Mineral oil
B) Alkylbenzene oil
C) Polyolester (POE) oil
D) PAG oil only for stationary
Answer: C - Polyolester (POE) oil POE oil is hygroscopic and miscible with
HFCs. Mineral oil is not miscible with HFCs and will cause oil return failure.
8. In a refrigeration cycle, where does subcooling occur?
A) In the evaporator outlet
B) In the condenser outlet / liquid line
C) At the compressor suction
D) At the expansion valve inlet only if flooded
Answer: B - In the condenser outlet / liquid line Subcooling is cooling liquid

, below its saturation temperature, ensuring 100% liquid to the metering device,
typically 8-15°F.
9. What is the result of non-condensable gases (air) in a refrigeration system?
A) Lower head pressure
B) Higher head pressure and higher discharge temperature
C) Lower suction pressure
D) No effect on pressures
Answer: B - Higher head pressure and higher discharge temperature Air
occupies condenser volume, reducing effective condensing surface and raising
head pressure, causing inefficiency and potential trip on high pressure.
10.A crankcase heater is used to?
A) Heat the conditioned space
B) Prevent refrigerant migration to the crankcase during off cycle
C) Increase oil viscosity
D) Boil off moisture in oil
Answer: B - Prevent refrigerant migration to the crankcase during off cycle
Refrigerant migration causes oil dilution and liquid slugging on startup. Heater
keeps crankcase warmer than evaporator.
11.What is the correct procedure for checking a hermetic compressor for a
ground?
A) Check resistance between Common and Start
B) Check resistance between any terminal and the compressor casing
C) Check voltage at terminals
D) Check capacitance
Answer: B - Check resistance between any terminal and the compressor
casing Low or zero resistance between C, S, or R terminal and the steel shell
indicates a grounded motor winding.
12.What is the purpose of a receiver in a refrigeration system?
A) To filter refrigerant
B) To store excess liquid refrigerant during varying load conditions
C) To separate oil from refrigerant
D) To meter refrigerant
Answer: B - To store excess liquid refrigerant during varying load conditions
Receiver accommodates charge variations in systems with TXV and is essential
for pump-down operation.

Document information

Uploaded on
October 26, 2026
Number of pages
30
Written in
2026/2027
Type
Exam (elaborations)
Contains
Questions & answers
$22.99

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
elitemindsA
3.8
(21)
Sold
90
Followers
5
Items
5103
Last sold
5 days ago



Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions