Connecticut (CT) L-6 Limited Electrical Journeyperson (Low Voltage) Practice Exam
Connecticut (CT) L-6 Limited Electrical Journeyperson (Low Voltage) Practice Exam
Connecticut (CT) L-6 Limited Electrical Journeyperson (Low Voltage) Practice Exam
Connecticut (CT) L-6 Limited Electrical Journeyperson (Low Voltage) Practice Exam
Connecticut (CT) L-6 Limited Electrical Journeyperson (Low Voltage) Practice Exam
Mostly Tested Exam Coverage Areas (Based on Connecticut L-6 Exam Content
Outline):
1. Fire Alarm Systems – initiating devices, notification appliances, control panels, and
NFPA 72 fundamentals 11
2. Security & Intrusion Systems – sensors, zones, EOL resistors, and control panel
programming 4
3. Audio & Sound Systems – speaker impedance, amplifier matching, and distributed
line calculations 6
, 4. Video Systems – CCTV cameras, coax/UTP transmission, and power supply
considerations
5. Access Control Systems – credential readers, electric strikes, REX devices, and fail-
safe vs. fail-secure
6. NEC Article 725 – Class 1, Class 2, and Class 3 power-limited circuits 6 11
7. NEC Article 760 – Fire alarm system wiring methods and cable ratings 11
8. NEC Article 800 – Communications circuits, cable substitutions, and separation
requirements 6 11
9. Connecticut L-6 Scope of Work – voltage/current limits, prohibited
telecommunications work, and contractor employment rules 1
10. General Low-Voltage Safety & Testing – grounding, bonding, multimeter usage, and
OSHA best practices 3
250 Randomized Practice Questions
,1. A low-voltage technician is installing a Class 2 circuit for a thermostat control and
needs to verify the maximum allowable voltage under normal operating conditions.
According to the NEC, what is the highest voltage permitted for a Class 2 circuit?
A. 12 volts
B. 24 volts
C. 30 volts
D. 48 volts
Correct Answer: C
Rationale: Class 2 circuits are inherently power-limited and restricted to a maximum of
30 volts to minimize fire and shock hazards under Article 725.
2. While terminating a Category 6 data cable in a commercial building, the electrician
must ensure the bend radius is not exceeded to prevent signal degradation. What is the
generally accepted minimum bend radius for a standard UTP cable?
A. One times the cable diameter
B. Two times the cable diameter
C. Four times the cable diameter
D. Ten times the cable diameter
Correct Answer: C
, Rationale: Exceeding a four-times-diameter bend radius can distort the twist geometry
of the pairs, leading to crosstalk and return loss failures.
3. A technician employed by an L-5 limited contractor is asked to repair a broken
telephone line inside a residential unit. Based on the Connecticut L-6 scope of work,
which statement is accurate?
A. The L-6 may repair the telephone line if the voltage is under 25 volts
B. The L-6 is prohibited from repairing telecommunication work except for specific
alarm interface wiring
C. The L-6 may repair the line only if supervised by an E-1 unlimited contractor
D. The L-6 may repair the line because it is considered low voltage
Correct Answer: B
Rationale: Connecticut regulations explicitly exclude general telecommunication repair
from the L-6 scope, allowing only the interface wiring from an alarm panel to an
existing telephone connection for monitoring.
4. During the installation of a fire alarm initiating device circuit, the technician
measures the circuit resistance and finds it is excessively high. What is the primary
operational risk associated with excessive resistance on an IDC?