Core Domains
Air Conditioning Heat Loads and Principles
Air Distribution Systems and Design
Refrigeration Components and Operation
Boilers and Pressure Vessels
Combustion Air and Fuel-Burning Equipment
Controls and Control Circuits
Electrical Systems and Troubleshooting
Business and Law
Technician Regulations and Compliance
Safety and Professional Standards
Introduction
The Environmental Air Conditioning Technician examination assesses the knowledge
and skills required to safely perform maintenance, service, and repair of
environmental air conditioning systems under the supervision of a licensed
contractor. The exam evaluates competence across foundational refrigeration theory,
applied system knowledge, regulatory compliance, electrical troubleshooting, and
professional judgment. Questions include both direct knowledge assessments and
,scenario-based applications requiring critical thinking and practical decision-
making. Candidates must demonstrate understanding of real-world service
situations and the ability to apply appropriate diagnostic and problem-solving
strategies consistent with industry standards and Texas regulations.
SECTION ONE
Questions 1–50
1. A technician is performing a load calculation for a residential structure. Which
factor has the greatest impact on the sensible cooling load?
A. Outdoor humidity ratio
B. Internal heat gain from occupants
C. Temperature difference across the building envelope
D. Latent heat from infiltration
🟢 Correct Answer: C. Temperature difference across the building envelope
🔴 Rationale: Sensible cooling load is primarily driven by temperature difference
(ΔT) between indoor and outdoor conditions through conduction and radiation
pathways. While internal gains and infiltration contribute, envelope heat transfer
due to temperature difference typically represents the dominant sensible load
component.
2. Which document provides the industry-accepted methodology for residential
heating and cooling load calculations?
A. Manual D
,B. Manual J
C. Manual N
D. Manual S
🟢 Correct Answer: B. Manual J
🔴 Rationale: ACCA Manual J is the recognized standard for residential load
calculations, providing procedures for determining heating and cooling loads
based on construction details, orientation, and climate data.
3. A technician measures a suction line temperature of 55°F and a suction
pressure corresponding to a saturation temperature of 40°F. What is the
superheat value?
A. 15°F
B. 25°F
C. 40°F
D. 55°F
🟢 Correct Answer: A. 15°F
🔴 Rationale: Superheat is calculated by subtracting the saturation temperature
from the actual suction line temperature. 55°F − 40°F = 15°F superheat.
4. A system operating with a thermostatic expansion valve has a suction
superheat of 3°F. What does this indicate?
A. The evaporator is starved
, B. The system is overcharged
C. The evaporator is flooded
D. The condenser is restricted
🟢 Correct Answer: C. The evaporator is flooded
🔴 Rationale: Low superheat indicates excessive liquid refrigerant is entering the
evaporator without fully vaporizing, creating risk of liquid floodback to the
compressor. Adequate superheat (typically 8–15°F) ensures complete evaporation.
5. A technician discovers a condenser coil that is heavily fouled with dirt and
debris. What effect will this condition have on system operation?
A. Decreased head pressure
B. Increased suction pressure
C. Increased head pressure
D. Decreased compressor amperage
🟢 Correct Answer: C. Increased head pressure
🔴 Rationale: A dirty condenser coil restricts heat rejection, causing refrigerant to
remain at higher temperatures and pressures. This elevated condensing pressure
increases compressor discharge pressure and amperage draw.
6. Which component in a refrigeration system separates the high-pressure side
from the low-pressure side?
A. Compressor