INSTANT PDF DOWNLOAD This document provides a focused NYC Master Electrician exam preparation test featuring carefully selected practice questions and analyzed solutions for the 2026 examination period. It covers essential electrical theory, calculations, wiring methods, grounding and bonding, motors, transformers, load calculations, safety requirements, and NYC Electrical Code topics. The material is designed to support structured revision and exam preparation, with an A+ grading designation for the document.

Content preview

NYC MASTER ELECTRICIAN EXAM
PREPARATION TEST WITH CAREFULLY
ANALYZED SOLUTIONS GRADED A+ 2026



Type ____ is multiconductor cable identified for use as underground service entrance
cable. ANSWER > Type USE cable

Knife switch rated for more than 1200 Amps at 250Volts or less ANSWER > Can be
used only as isolating switch, shall not be opened under load

Track lighting with outlets in a bathroom is not allowed because ? ANSWER > Track
lighting has receptacle

Where internal combustion engines are used as the prime motor, an on site fuel supply
shall be provided with an on premise fuel supply sufficient for not less than ____ hours
full demand operation of the system ANSWER > 6 hours




1

,Fixed in place X-ray equipment properly supplied by a branch circuit rated at not over
____ amperes shall be permitted to be supplied through a suitable attachment plug cap
and hard service cable cord. ANSWER > 30 Amps

Where skin effect exist the ferromagnetic envelope shall be bonded at ____. ANSWER
> Both ends

GFCI protection at a carnival is not required for equipment at circuit if the receptacle is
of the ____type. ANSWER > Locking

The maximum voltage drop from service point to the last over-current device in a
dwelling unit? ANSWER > 4%

Which of the following statements best describe the grounding requirement for central
vacuum outlet ANSWER > Accessible non current carrying metal parts are required to
be connected to an equipment grounding conductor.

In healthcare facilities, patient bed receptacles located in general care areas shall be
supplied by at least two branch circuits, which ____permitted to originate from two
separate transfer switches on the emergency system ANSWER > Are permitted

Patient care areas of healthcare facilities ____ areas such as business offices,
corridors, lounges ,day rooms, or similar areas ANSWER > Do not include

The patient care area is any portion of the healthcare facility where patients are
intended to be ____or ____. ANSWER > Examined or treated

Each general care area patient bed location in a healthcare facility must be provided
with four ____ or ____ duplex receptacles ANSWER > Single or two

A hospital is a building or portion thereof used for medical, psychiatric,obstetrical , or
surgical, care on a 24 hour basis of ____ or more patients ANSWER > Four

Where installed to reduce electrical noise for electronic equipment, electrical continuity
of the metal raceways shall not be required and metal raceway can terminate a (an)
____ nonmetallic fitting or spacer on electronic equipment ANSWER > Listed fitting

Feeder and branch circuit conductors within ____ inches of a Ballast shall have an
insulation temperature rating not lower than 90°C (194°F) unless supplying a luminaiere
marked as suitable for a different insulation temperature ANSWER > 3 inches

Manufactured wiring systems constructed with type MC cable shall be supported and
secured at intervals not exceeding ____ ft. ANSWER > 6 ft




2

,Where a main bonding jumper or a system bonding jumper is a screw only the screw
shall be identified with a ____ that shall be visible with the screw installed ANSWER >
Green finish

Plug fuses a 15 amperes and lower rating shall be identified by a ____ configuration of
the window, cap, or other prominent part to distinguish them from fuses of higher
ampere rating ANSWER > Hexagon

The load for household electric clothes dryer's in a dwelling unit(s) shall be either ____
watts (volt-amperes) or the nameplate rating, which ever is larger, for each dryer served
? ANSWER > 5000 watts

Service conductors installed as unjacketed multiconductor cable shall have a minimum
clearance of ____ windows that are designed to be opened, doors, porches, stairs fire
escape or similar locations. ANSWER > 3 ft (36 inches)

—— Cartridge fuses of the renewable type shall be permitted to be used only for
replacement in existing installation is where there is no evidence of over-fusing or
tampering. ANSWER > Class H

Branch circuit conductors within ____inches of the ballast shall have an insulation
temperature rating not lower it 90°C 194°F ANSWER > 3" inches

The minimum radius of a field bend on trade size 1 "1/4 RMC is ____. ANSWER > 8

In a dwelling unit which appliance is allowed to have a 24"inch cord with Attachment
ground plug ? ANSWER > Combination range hood/microwave oven

Type 3 Surge Protective devices can be installed on the load side of a branch circuit
overcurrent device up to the equipment served.if ____ the type 3 SPD connection must
be a minimum 30'ft of conductor a distance from the service or separately derived
system disconnect ANSWER > Included in the manufactures instructions

Which flexible cable is Allowed to be used for electric vehicle charging station 300 Volts
? ANSWER > EVJ

Type ____ fuse adapters shall be designed so that once inserted in a fuse holder that
cannot be removed ANSWER > Type S fuse

Service drops Installed over roof shall have a vertical clearance of ____ above the roof
surface, and unless a lesser distance is permitted by and exceptions ANSWER > 8'ft

Class 2 and Class 3 circuits shall not be placed in any enclosure, raceway, cable, or
similar fittings with conductors of Class 1 or electric light or power conductors, unless
____. ANSWER > Separated by barrier

3

, In the critical care areas of health care centers, each patient bed shall be provided with
a minimum of ____ duplex receptacles ANSWER > 3 duplex (6 single)

The equipment system shall supply major electric ____ necessary for patient care and
basic hospital operation ANSWER > Equipment

The essential electrical system in a healthcare facility shall be compromised of the
ANSWER > emergency system and the: equipment system

Locations were flammable anesthetics are employed are class I,Division I locations that
shall extend ANSWER > upwards to a level 5'ft above the floor

In a healthcare facility receptacles and attachment plugs in a hazardous (classified)
location with an anesthizing area shall be listed for use in class I group ____ locations
ANSWER > Group C

In anesthetic,areas health care equipment frequently in contact with bodies of persons
shall not exceed ____ volts. ANSWER > 10 Volts

In anesthetic areas, low-voltage equipment that is frequently in contact with the bodies
of persons or has exposed current-carrying elements shall ANSWER > operate on an
electrical potential of 10 volts or less,be moistur- resistant, be approved as intrinsically
safe or double-insulated equipment.

In a healthcare facility, the maximum internal current permitted to flow through a line
isolated monitor,when any point of the isolated system is grounded, shall be ____ .
ANSWER > 1 milliamperes

Transfer eguipment, including automatic transfer switches,shall be ANSWER >
automatic, identified for emergency use , approved by the authority having jurisdiction

Automatic transfer switches shall be ____ operated and ____ held ANSWER >
Electrically operated and mechanically

Audible and visual signal devices for an emergency system shall be provided,where
practicable, for the purpose(s) of indicating that ANSWER > the battery is carrying load,
derangement of emergency source, that the battery charger is not functioning

Wiring from an emergency source to emergency loads shall ____ ____ ____ ____ of all
other wiring ANSWER > Be kept entirely independent of all other wiring

Emergency circuit wiring shall be permitted to enter which of the following types of
equipment with normal circuit wiring? ANSWER > Transfer switches, exit or emergency
luminaries supplied from two sources


4

Document information

Uploaded on
September 20, 2026
Number of pages
39
Written in
2026/2027
Type
Exam (elaborations)
Contains
Questions & answers
$10.99

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Sold
11
Followers
2
Items
504
Last sold
3 weeks ago




Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions