WITH ACCURATE ANSWERS |RATED 100% .
Assembly Occupancy's are buildings used for gathering of _____ or more people for
deliberation, worship, entertainment, eating, drinking, amusement, awaiting transportation or
similar. - correct Answers -50 people
Class 3 wiring installed under roof decking is required to be at least __ inches below the roof
decking - correct Answers -1.5 Inches
The minimum length of free conductors at outlet boxes is - correct Answers -6 Inches
A ________ ___ is required for each splice or termination point. - correct Answers -Junction
Box
Wiring inside ducts is not permitted unless - correct Answers -the wiring applies to the direct
functioning of the duct system.
Wiring or raceway installed in environmental air return spaces is required to be ______ - correct
Answers -Plenum rated.
The installation of wiring cannot impede the removal of - correct Answers -ceiling tiles
The Minimum size for EMT is - correct Answers -1/2 Inches
The Maximum size of E.M.T is - correct Answers -4 Inches
E.M.T is required to have a maximum of ___ degrees of bends between pull points - correct
Answers -360
1
,EMT is required to be secured ever __ feet - correct Answers -10
E.M.T is required to be secured withing _ feet of a box - correct Answers -3
E.M.T is _________ to be used as an equipment grounding donductor - correct Answers -
permitted.
Class 1 wiring is limited to ___ volts - correct Answers -600
Class 2 wiring is limited to ___ volts - correct Answers -150
Class 3 wiring is limited to __ volts - correct Answers -30
When located within _ feet of the floor FPL wire is required to be protected - correct Answers -7
FPL circuit cable can be as small as __ gauge when using multi-conductor cable. - correct
Answers -26
If an individual conductor is used as part of a FPL circuit, the minimum conductor size is __
gauge - correct Answers -18
FPL Fire alarm cable - correct Answers -This type of cable is suitable for horizontal wire runs on
a single floor. The plastic coating which provides the insulation for the cable is flammable and
produces a toxic gas when burned.
FPLR Fire alarm cable (Riser) - correct Answers -This type of cable is suitable for vertical
wiring between floors. It is resistant to burning. It produces a toxic gas when burned.
2
, FPLP Fire alarm cable (Plenum) - correct Answers -This type of cable is highest rated. FPLP
cable is suitable for use in spaces used for environmental air return. It does not produce toxic gas
when burned.
What are permitted substitutions for FPL - correct Answers -CM, CMG, FLPR, CMR, FPLP,
CMP
What are permitted substitutions for FPLR - correct Answers -CMR, FPLP, CMP
What are permitted substitutions for FPLP - correct Answers -CMP
The Americans with Disabilities Act was enacted in which year? - correct Answers -1990
On a given floor of a building, manual pull boxes shall be located such that no horizontal travel
distance between pull boxes exceeds _____________. - correct Answers -200 Feet
Where specifically permitted, which occupancy type is exempt from audible notification
requirements? - correct Answers -Health Care
Which of the following terms are you not likely to come across, as it pertains to Building
Rehabilitation? - correct Answers -Removal
To be considered a Residential Occupancy, an apartment building must contain ______ or more
dwelling units. - correct Answers -Three
Automatic detection is required in Assembly Occupancies with loads greater than ____. - correct
Answers -300
With a delayed egress locking system, the door must be immediately unlocked upon
_____________. - correct Answers -loss of power
3