●● The cross-sectional area of three or more THW conductors in a
conduit must not exceed what percent of the cross-sectional area of the
conduit?
A) 30%
B) 40%
C) 50%
D) 60%
Answer: B) 40 %
Chapter 9 Table 1
●● EMT must be supported within what distance from an outlet box,
junction box, device box, cabinet, conduit body or other terminations?
A) 3 feet
B) 4 feet
C) 5 feet
,D) 6 feet
Answer: A) 3 feet
Article 358.30 (A)
●● When a branch circuit feeds both noncontinuous and continuous
loads, the circuit must be sized to accommodate 100% of the
noncontinuous load plus what percent of the continuous load?
A) 110%
B) 115%
C) 120 %
D) 125%
Answer: D) 125%
Article. 210.20 (A)
●● What is the allowable Ampacity of a 600 MCM copper conductor
type TW?
A) 300 Amps
B) 350 Amps
C) 355 Amps
,D) 400 Amps
Answer: B) 350 Amps
Table- 310.16
●● The name given to a system or circuit conductor that is intentionally
grounded is?
A) Grounding Conductor
B) Bonding Conductor
C) High-leg conductor
D) Grounded or neutral conductor
Answer: D) Grounded or Neutral Conductor
Article 100 Definitions
●● The panels of switchboards must be made of?
A) Moisture resistant, noncombustible material
B) Raintight material
C) Impact-resistant material
, D) Waterproof material
Answer: A) Moisture-resistant, noncombustible material
Article 408.50
●● A metal pole supporting a light fixture shall have an accessible
handhole not less than ________ inches?
A) 2 X 6 inches
B) 3 X 4 inches
C) 2 X 4 inches
D) 4 X 8 inches
Answer: C) 2 X 4 inches
Article 410.30 (B) (1)
●● The largest standard rating for fuses and inverse time circuit breakers
is?
A) 1000 amps
B) 1600 amps
C) 1200 amps
D) 6000 amps
ASSESSMENT 2026 TEST BANK QUESTIONS
AND SOLUTIONS GRADED A+
●● The cross-sectional area of three or more THW conductors in a
conduit must not exceed what percent of the cross-sectional area of the
conduit?
A) 30%
B) 40%
C) 50%
D) 60%
Answer: B) 40 %
Chapter 9 Table 1
●● EMT must be supported within what distance from an outlet box,
junction box, device box, cabinet, conduit body or other terminations?
A) 3 feet
B) 4 feet
C) 5 feet
,D) 6 feet
Answer: A) 3 feet
Article 358.30 (A)
●● When a branch circuit feeds both noncontinuous and continuous
loads, the circuit must be sized to accommodate 100% of the
noncontinuous load plus what percent of the continuous load?
A) 110%
B) 115%
C) 120 %
D) 125%
Answer: D) 125%
Article. 210.20 (A)
●● What is the allowable Ampacity of a 600 MCM copper conductor
type TW?
A) 300 Amps
B) 350 Amps
C) 355 Amps
,D) 400 Amps
Answer: B) 350 Amps
Table- 310.16
●● The name given to a system or circuit conductor that is intentionally
grounded is?
A) Grounding Conductor
B) Bonding Conductor
C) High-leg conductor
D) Grounded or neutral conductor
Answer: D) Grounded or Neutral Conductor
Article 100 Definitions
●● The panels of switchboards must be made of?
A) Moisture resistant, noncombustible material
B) Raintight material
C) Impact-resistant material
, D) Waterproof material
Answer: A) Moisture-resistant, noncombustible material
Article 408.50
●● A metal pole supporting a light fixture shall have an accessible
handhole not less than ________ inches?
A) 2 X 6 inches
B) 3 X 4 inches
C) 2 X 4 inches
D) 4 X 8 inches
Answer: C) 2 X 4 inches
Article 410.30 (B) (1)
●● The largest standard rating for fuses and inverse time circuit breakers
is?
A) 1000 amps
B) 1600 amps
C) 1200 amps
D) 6000 amps