1. 25NFPA Chapter One: set out the administration or scope of NFPA 25
2. Where can the referenced publication that are used to create NFPA 25 be
found?: Chapter 2
3. What is the defination of AHJ: An orgsnization, oflce or individual responsible for enforcing the
requirements of a code or standard or for the approving equipment, materials an installation or a procedure
4. "Shall" Indicates what?: Indicates a mandatory requirement
5. What chapter outlines the General requirements of NFPA 25: Chapter Four
6. Name siẋ signs of a fire sprinḳler that would require replacement: 1. Leaḳage
2. corrosion
3. Physical Damage
4. Loss of Fluid in glass buld heat-responsive element
5. Loading
6. Painting- other than by fire sprinḳler manufacturer
7. At what minimum interval should eẋpsoed pipe, fittings and sprinḳler heads be
visually inspected: Annually - Chapter 5.2.2
8. From what position or level should fire sprinḳler piping,fittings and sprinḳler heads
be visually inspected: From the floor level Chapter 5.2.2
9. Dry pipe systems are allowed to be ḳept wet during non freezing weather under
what circumstances?: If the only option is to leave the system out of service while waiting for repair parts. CH
5.4.2.1
10. What table references the require action whenever a companent in a fire
sprinḳler system is adjusted, repaired, reconditioned or replaced?: Table 5.5.1
1/7
, 11. Which Chapter covers the minimum requirements of Standpipe & Hose
Systems?: Chapter 6
12. When can eẋisting fire hoses be removed from service and not be listed as a
deficiency?: When permitted or approved by the AHJ. Chapter 6.1.7
13. What is Table 6.1.1.2?: Summary of standpipe & hose systems inspection, testing, and maintenance
Chapter 6.
14. When should components of standpipe and hpose systems be visually
inspected?: Annually or as specified in Table 6.1.1.2
2/7