Question 1
On a standard pilot gas furnace, the thermocouple should be
replaced when:
• A) The millivolt reading is 25 or higher
• B) The millivolt reading is 23 or lower
• C) The millivolt reading is 30 or higher
• D) The millivolt reading is exactly 15
Correct Answer: B
Rationale: A properly functioning thermocouple should produce
25-30 millivolts (mV). When the reading drops to 23 mV or lower,
the thermocouple is weak and cannot hold the pilot safety valve
open, causing the pilot to go out. Replacement is necessary. The
thermocouple generates DC voltage from heat and is a critical
safety device that shuts off gas if the pilot goes out.
,Question 2
Natural gas pressure at the main line is recorded at 7" WC but at
the gas manifold it reads 1.5" WC. What could be the problem
with the furnace?
• A) A defective gas valve
• B) A defective regulator in the gas valve
• C) A clogged main gas line
• D) A defective thermocouple
Correct Answer: B
Rationale: The gas valve contains an internal pressure regulator
that reduces the main line pressure (typically 7" WC for natural
gas) to the manifold pressure (typically 3.5" WC for natural gas). A
reading of 1.5" WC indicates the regulator is defective (not
maintaining proper pressure). This low manifold pressure will
result in small flames, delayed ignition, and poor heating
performance.
, Question 3
A tech servicing a gas fired unit notices 4 out of 5 ribbon burners
are firing simultaneously. What could be a problem with the
system?
• A) Burners not properly aligned
• B) Gas pressure too high
• C) Defective thermocouple
• D) Clogged burner orifices
Correct Answer: A
Rationale: When burners are not firing simultaneously (only 4 out
of 5), it is typically because the burners are misaligned. Burner
alignment is critical for proper cross-lighting. If burners are not
properly aligned, the flame from one burner will not carry over to
ignite the next burner, causing delayed ignition or uneven firing.