S-12 CITYWIDE SPRINKLER SYSTEMS,
S12 sprinkler test 2026 Exam complete
exam questions and answers 2026
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE QUALIFICATIONS. -
CORRECT ANSWERS OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A MIN. OF
__________ YEARS. - CORRECT ANSWERS 3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH REQUIREMENTS. -
CORRECT ANSWERS IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S) ARE CONSIDERED
PLANNED REMOVAL FROM SERVICE. - CORRECT ANSWERS 1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED UNPLANNED OUT OF
SERVICE CONDITIONS. - CORRECT ANSWERS 1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO SERVICE WITHIN ______
HOURS. - CORRECT ANSWERS 8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY REPORT CONDITION
TO THE ___________ AND THE FIRE DEPT. - CORRECT ANSWERS OWNER OF THE
BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS OR IT WILL BE
CONSIDERED AN IMPAIRMENT. - CORRECT ANSWERS 30
,WHAT DOES "OOS" STAND FOR? - CORRECT ANSWERS OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT. CONNECTIONS, SYS. CONTROL
VALVES, AND FIRE COMMAND CENTER - CORRECT ANSWERS TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY SECTIONAL VALVES.
- CORRECT ANSWERS MASTER FIRE SUPPRESSION PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW PRESSURES BEFORE
AND AFTER. - CORRECT ANSWERS DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________. - CORRECT ANSWERS NO IMPAIRMENT WAS
FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - CORRECT ANSWERS MAIN
CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG PLACED ON THE
MAIN CONTROL VALVE. - CORRECT ANSWERS RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM IS
FULLY OUT OF SERVICE. - CORRECT ANSWERS WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM IS
PARTIALLY OUT OF SERVICE. - CORRECT ANSWERS BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER, CENTRAL STATION AND
OCCUPANTS. - CORRECT ANSWERS INSURANCE
, PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT NECESSARY TESTS
AND INSPECTIONS ARE CONDUCTED. - CORRECT ANSWERS IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER THAN ________
PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - CORRECT ANSWERS 50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE ____________. -
CORRECT ANSWERS MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE DEPT. THESE ARE TO
BE MAINTAINED ON SITE FOR 3 YEARS. - CORRECT ANSWERS RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND COURT PROCEEDINGS. -
CORRECT ANSWERS REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD THE FOLLOWING
CERTS: - CORRECT ANSWERS REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE
OPERATING ENGINEER, AND NYS HIGH PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND SPRINKLER SYSTEMS.
- CORRECT ANSWERS MASTER FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH _________
SPRINKLER HEADS OR LESS. - CORRECT ANSWERS 30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN SPRINKLERS ARE
INSTALLED. - CORRECT ANSWERS 96
WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO PREVENT THE SYSTEM FROM
FREEZING. - CORRECT ANSWERS 40 FAHRENHEIT
S12 sprinkler test 2026 Exam complete
exam questions and answers 2026
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE QUALIFICATIONS. -
CORRECT ANSWERS OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A MIN. OF
__________ YEARS. - CORRECT ANSWERS 3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH REQUIREMENTS. -
CORRECT ANSWERS IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S) ARE CONSIDERED
PLANNED REMOVAL FROM SERVICE. - CORRECT ANSWERS 1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED UNPLANNED OUT OF
SERVICE CONDITIONS. - CORRECT ANSWERS 1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO SERVICE WITHIN ______
HOURS. - CORRECT ANSWERS 8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY REPORT CONDITION
TO THE ___________ AND THE FIRE DEPT. - CORRECT ANSWERS OWNER OF THE
BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS OR IT WILL BE
CONSIDERED AN IMPAIRMENT. - CORRECT ANSWERS 30
,WHAT DOES "OOS" STAND FOR? - CORRECT ANSWERS OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT. CONNECTIONS, SYS. CONTROL
VALVES, AND FIRE COMMAND CENTER - CORRECT ANSWERS TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY SECTIONAL VALVES.
- CORRECT ANSWERS MASTER FIRE SUPPRESSION PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW PRESSURES BEFORE
AND AFTER. - CORRECT ANSWERS DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________. - CORRECT ANSWERS NO IMPAIRMENT WAS
FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - CORRECT ANSWERS MAIN
CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG PLACED ON THE
MAIN CONTROL VALVE. - CORRECT ANSWERS RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM IS
FULLY OUT OF SERVICE. - CORRECT ANSWERS WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM IS
PARTIALLY OUT OF SERVICE. - CORRECT ANSWERS BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER, CENTRAL STATION AND
OCCUPANTS. - CORRECT ANSWERS INSURANCE
, PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT NECESSARY TESTS
AND INSPECTIONS ARE CONDUCTED. - CORRECT ANSWERS IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER THAN ________
PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - CORRECT ANSWERS 50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE ____________. -
CORRECT ANSWERS MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE DEPT. THESE ARE TO
BE MAINTAINED ON SITE FOR 3 YEARS. - CORRECT ANSWERS RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND COURT PROCEEDINGS. -
CORRECT ANSWERS REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD THE FOLLOWING
CERTS: - CORRECT ANSWERS REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE
OPERATING ENGINEER, AND NYS HIGH PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND SPRINKLER SYSTEMS.
- CORRECT ANSWERS MASTER FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH _________
SPRINKLER HEADS OR LESS. - CORRECT ANSWERS 30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN SPRINKLERS ARE
INSTALLED. - CORRECT ANSWERS 96
WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO PREVENT THE SYSTEM FROM
FREEZING. - CORRECT ANSWERS 40 FAHRENHEIT