Medical Gas Class
Study online at https://quizlet.com/_3mcoou
1. Category 1 medical -surgi- Two
cal vacuum sources shall,
at minimum, consist of
______ or more vacuum
pumps
2. Category 1 medical surgi- Backflow
cal vacuum sources shall
consist of an automatic
means too prevent _____
through any off -cycle vac-
uum pump
3. Piping between the vacu- True
um pump and the source
shutoff valve shall be per-
mitted to be stainless,
galvanized, or black steel
pipe
4. Vacuum receiver shall be 30"
capable of withstanding a
gauge vacuum of ______ of
mercury
5. The medical surgical vacu- Any method to ensure continuation service
um receiver shall be made
serviceable without shut-
ting down the system by
_______
6. When the medical surgical Automatically
I'm an operation is inca-
, Medical Gas Class
Study online at https://quizlet.com/_3mcoou
pable of adequately main-
taining a required vacu-
um, additional pump shall
be _______ activated
7. The medical surgical Any non-corroding material
vacuum exhaust shall
be turned down and
screened. The screened
shall be fabricated using
what type of material?
8. Multiple vacuum pumps Minimize back pressure
shall be permitted to be
join together to come one
common exhaust provid-
ed the common exhaust is
size to ______.
9. Vacuum exhaust from Blind flange, manual valve, check valve
multiple pumps join to-
gether to one common
exhaust shall be permit-
ted provided each pump
can be isolated by a _____.
10. Category 1 medical-sur- Local
gical vacuum systems
shall activate which alarm
when the backup or lag
pump is running?
11. Two
, Medical Gas Class
Study online at https://quizlet.com/_3mcoou
A level 1 dedicated WAGD
source shall consist of
______ or more producers,
each shall be sufficient to
serve the peak calculated
demand.
12. What source shall not be Medical air
used to power the venturi
of a WAGD system?
13. WAGD vacuum producers 5"
designed for operation at
vacuums below ____ Hg/V
shall be used only for
WAGD service and not em-
ployed for other services.
14. A WAGD source system Local
shall activate the ____
alarm when the backup or
lag producer is running.
15. Additional WAGD produc- Automatically
ers shall be ________ acti-
vated when the produc-
er(s) in operation is inca-
pable of maintaining re-
quired vacuum.
16. Medical air supply sys- Meet the requirements of medical air USP, have no detectable liquid
tems shall be required to hydrocarbons, have less than 25 ppm gaseous hydrocarbons
_____.
Study online at https://quizlet.com/_3mcoou
1. Category 1 medical -surgi- Two
cal vacuum sources shall,
at minimum, consist of
______ or more vacuum
pumps
2. Category 1 medical surgi- Backflow
cal vacuum sources shall
consist of an automatic
means too prevent _____
through any off -cycle vac-
uum pump
3. Piping between the vacu- True
um pump and the source
shutoff valve shall be per-
mitted to be stainless,
galvanized, or black steel
pipe
4. Vacuum receiver shall be 30"
capable of withstanding a
gauge vacuum of ______ of
mercury
5. The medical surgical vacu- Any method to ensure continuation service
um receiver shall be made
serviceable without shut-
ting down the system by
_______
6. When the medical surgical Automatically
I'm an operation is inca-
, Medical Gas Class
Study online at https://quizlet.com/_3mcoou
pable of adequately main-
taining a required vacu-
um, additional pump shall
be _______ activated
7. The medical surgical Any non-corroding material
vacuum exhaust shall
be turned down and
screened. The screened
shall be fabricated using
what type of material?
8. Multiple vacuum pumps Minimize back pressure
shall be permitted to be
join together to come one
common exhaust provid-
ed the common exhaust is
size to ______.
9. Vacuum exhaust from Blind flange, manual valve, check valve
multiple pumps join to-
gether to one common
exhaust shall be permit-
ted provided each pump
can be isolated by a _____.
10. Category 1 medical-sur- Local
gical vacuum systems
shall activate which alarm
when the backup or lag
pump is running?
11. Two
, Medical Gas Class
Study online at https://quizlet.com/_3mcoou
A level 1 dedicated WAGD
source shall consist of
______ or more producers,
each shall be sufficient to
serve the peak calculated
demand.
12. What source shall not be Medical air
used to power the venturi
of a WAGD system?
13. WAGD vacuum producers 5"
designed for operation at
vacuums below ____ Hg/V
shall be used only for
WAGD service and not em-
ployed for other services.
14. A WAGD source system Local
shall activate the ____
alarm when the backup or
lag producer is running.
15. Additional WAGD produc- Automatically
ers shall be ________ acti-
vated when the produc-
er(s) in operation is inca-
pable of maintaining re-
quired vacuum.
16. Medical air supply sys- Meet the requirements of medical air USP, have no detectable liquid
tems shall be required to hydrocarbons, have less than 25 ppm gaseous hydrocarbons
_____.