As per 3 RCNY §15-02, "Portable Fire Extinguishers", an
inspection of a portable fire extinguisher which is intended to
give reasonable assurance that the fire extinguisher is fully
charged and operable, and is in its designated place, not
tampered with, and has no visible physical damage or condition
to prevent its operation, is called
A. A "quick check" inspection
B. A "double check" inspection
C. An "educated check" inspection
D. A "new method" inspection - ANSWER-A. A "quick check"
inspection
As per 3 RCNY §15-02, "Portable Fire Extinguishers", portable
fire extinguishers shall be provided in occupancies or spaces
used or classified as offices, hotels and motels. In fully
sprinklered buildings classified as offices or places of worship,
they shall provide one fire extinguisher of minimum 2-A rating
for every
,A. 14,000 square feet of floor area or fraction thereof on each
floor
B. 12,000 square feet of floor area or fraction thereof on each
floor
C. 10,000 square feet of floor area or fraction thereof on each
floor
D. 8, 000square feet of floor area or fraction thereof on each floor
- ANSWER-B.
12,000 square feet of floor area or fraction thereof
on each floor
In hotels and motel, there should be one fire extinguisher of a
minimum of
2-A rating for every 6,000 square feet of floor area or
part thereof
A. Sprinklered or not.
B. if unsprinklered
C. if more than half sprinklered
D. if more than 3/4 sprinklered - ANSWER-A. Sprinklered or not.
,For both Class E and J-1 buildings, sprinklered or not, fire
extinguishers
(minimum 2-A rating) shall be located so that the travel
distance to an
extinguisher shall not exceed how
many feet?
A. 70 feet
B. 50 feet
C. 100 feet
D. 75 feet - ANSWER-D. 75 feet
Extinguishers must be conspicuously located, along the
normal paths of
travel. For extinguishers 40 lbs or less, the top of the
extinguisher can not be
higher than how many feet above
the floor?
A. 5 feet
B. 4 feet
C. 6 feet
D. 3 feet - ANSWER-A. 5 feet
, For extinguishers greater than 40 lbs in weight, the top of the
extinguisher
can not be more than how many feet
above the floor
A. 3½ feet
B. 4½ feet
C. 3 feet
D. 4 feet - ANSWER-A. 3½ feet
Regardless of how much a fire extinguisher weighs, how much
clearance
must there be between the bottom of the extinguisher
and the floor?
A. at least 4½" of clearance
B. at least 4" of clearance
C. at least 3" of clearance
D. at least 3½" of clearance - ANSWER-B. at least 4" of clearance
Extinguishing Systems for Hoods, Vent Pipes, Flues or Ducts
are regulated by RCNY §15-04. The extinguishing system shall