The local agency must do all of the following in conjunction with red tagging a
facility with significant violations that do not pose an imminent threat to human
N
health or safety, EXCEPT,
O
T
a. Issue a notice of significant violation(s) identifying the significant violations.
C
O
b. If the owner/operator fails to correct the significant violations the local agency
may attach a red tag.
PY
c. Take pictures to document the violation
d. Document the level of stored product in the tank.
c. Take pictures to document the violation
CCR; 2717.1
The regulations to enforce compliance of underground storage tank systems in the
state are found in?
,a.) Code of Federal Regulations, 40 CFR Part 281
b.) California Code of Regulations, Title 23, Chapter 16
c.) Code of Federal Regulations, 40 CFR Part 280
d.) California Code of Regulations, Title 23, Chapter 17
b.) California Code of Regulations; Title 23, Chapter 16
By definition an "underground storage tank system" includes
a.) The tank, all connected piping and dispensers
D
b.) The tank, all connected piping, ancillary equipment and containment system c.)
O
Only the tank
N
d.) Only tanks totally beneath the surface of the ground
O
b.) The tank, all connected piping, ancillary equipment and containment
T
system (H&SC, Sec 25281(z))
C
O
PY
The written report submitted to the local agency after an unauthorized release is
required to include the following except:
a.) Description of actions taken to stop the release
b.) Cause of the release
c.) Method of disposal of released product
d.) Date on which the release was discovered
b.) Cause of the release
CCR Title 23, Sec 2652(c)
,What person(s) is required to maintain evidence of financial responsibility?
a. The UST operator
b. The UST owner
c. The owner of the property where the UST is sited
d. The UST owner and the UST operator
d. The UST owner and the UST operator
H≻ 25292.2
D
O
When an ATG system is used to monitor a tank, a 0.2 gallon/hour leak test must be
N
performed:
O
T
a. At least once daily.
C
b. At least once monthly.
O
c. At least once yearly.
PY
d. As specified by the equipment manufacturer.
b. At least once monthly.
CCR; 2643 (b)
If the owner/operator fails to correct a significant violation within _________
business day(s) from receipt of the notice, the local agency may affix a red tag to
the fill pipe of the non-compliant UST system:
, a.) Three
b.) Five
c.) Seven
d.) Same day
c.) Seven
CCR Title 23, Sec 2717.1(b)
D
O
When an automatic tank gauge is utilized to monitor a single-walled tank, a 0.2
N
gallon/hour leak test must be performed:
O
T
a.) At least once daily
C
b.) As specified by the equipment manufacturer
O
c.) At least once monthly
PY
d.) At least once yearly
c.) At least once monthly
CCR Title 23, Sec 2643(b)(1)
Automatic line leak detectors shall be installed on underground pressurized piping
with secondary containment and shall be capable of detecting a: