1. Light sources used for testing sensitivity on 1) Measured Energy Output
radiant energy detectors must meet which of 2) Defined distance for testing.
the following requirements?
2. Air sampling detectors are required to be test- Annually
ed?
3. A 25% increase in port pressure is acceptable? False. An increase of that amount indi-
cates a major change or problem.
4. In air sampling detection systems a decrease False. Test valves should be closed to
in smoke transport times would be accept- the valves measured during commis-
able? sioning.
5. Air Sampling detectors are required to be in- Semiannually
spected?
6. Radiant Energy Detectors must be tested Semiannually
7. Two Way emergency Communication sys- Annually
tems must be tested?
8. True or False? You must scan the disk storage FALSE
for bad sectors as a requirement for testing
of the control unit for a Mass Notification Sys-
tem?
9. True or False? You must Power down the unit TRUE
and restart it when testing the control unit for
a Mass Notification System?
10. True or False? You must delete unneeded log TRUE
and error files as par of the required testing
, Inspect & Test Fire Alarm NICET 2
Inspect & Test Fire Alarm NICET 2
Study online at https://quizlet.com/_a30pk7
for the control unit of Mass Notification Sys-
tems?
11. True or False? When testing the control unit of TRUE
a Mass Notification System; verify any remote
control software loaded into the system is dis-
abled to prevent unauthorized access.
12. Which is NOT a form of Emergency Communi- Audible Zone Alert
cation System;
1) Fire fighters Phone
2) Mass notification System
3) One way communication system
4) Audible Zone Alert
13. Radiant Energy Detectors must be inspected? Quarterly
14. When testing a Mass Notification system, dur- disconnect
ing the test of the main power supply, you
must first ________________ the secondary pow-
er supply and test under maximum load.
15. Gasoline fires generate energy in which spec- 1) UV
trum(s) 2) IR
3) Visible
16. True or False? The only inspection task for FALSE
radiant energy detectors is to verify no point
requiring detection is outside of the detec-
tor's field of view?
17. In order to test an air sampling detector sys- the end sampling port on each pipe
tem ___________________. must be tested.