NICET 1- Test and Inspection
NICET 1- Test and Inspection
Study online at https://quizlet.com/_df049u
1. Unless otherwise recommended by the manufactur- SMOKE ALARMS, 10 YEARS
er's published instructions, ___________________ (120V
residential smokes) installed in one and 2 family
dwellings shall be replaced every__________ from date
of manufacture. (NFPA 72, Ch 14)
2. Household fire alarm system smoke detectors shall be ANNUALLY
tested by a technician ______________
3. ______________shall be visibly inspected by confirming Strobe lights
that the candela rating marking agrees with the ap-
proved drawings.
4. Inspection, testing, or maintenance of the FAS shall be IT IS CONDUCTED UNDER
permitted to be done by the building or system owner WRITTEN CONTRACT
or a person or organization other than the building or
system owner if
____________________________________________________________.
5. When a non-restorable, fixed temperature, line type THE SYSTEM OWNER.
heat detector is tested annually, the testing records
shall be kept by ______________________________.
6. If the operation of a device, circuit, control function, IT SHALL BE NOTED THAT
or special hazard interface is simulated during a test, IT WAS SIMULATED
_____________________________________________________________________
on the inspection report.
7. The MINIMUM number of RESTORABLE FIXED TEM- (2) or MORE
PERATURE SPOT TYPE heat detectors that must be test-
ed annually is _______________ on each initiating circuit.
(NFPA 72, Ch 14)
1/2
NICET 1- Test and Inspection
Study online at https://quizlet.com/_df049u
1. Unless otherwise recommended by the manufactur- SMOKE ALARMS, 10 YEARS
er's published instructions, ___________________ (120V
residential smokes) installed in one and 2 family
dwellings shall be replaced every__________ from date
of manufacture. (NFPA 72, Ch 14)
2. Household fire alarm system smoke detectors shall be ANNUALLY
tested by a technician ______________
3. ______________shall be visibly inspected by confirming Strobe lights
that the candela rating marking agrees with the ap-
proved drawings.
4. Inspection, testing, or maintenance of the FAS shall be IT IS CONDUCTED UNDER
permitted to be done by the building or system owner WRITTEN CONTRACT
or a person or organization other than the building or
system owner if
____________________________________________________________.
5. When a non-restorable, fixed temperature, line type THE SYSTEM OWNER.
heat detector is tested annually, the testing records
shall be kept by ______________________________.
6. If the operation of a device, circuit, control function, IT SHALL BE NOTED THAT
or special hazard interface is simulated during a test, IT WAS SIMULATED
_____________________________________________________________________
on the inspection report.
7. The MINIMUM number of RESTORABLE FIXED TEM- (2) or MORE
PERATURE SPOT TYPE heat detectors that must be test-
ed annually is _______________ on each initiating circuit.
(NFPA 72, Ch 14)
1/2