NICET fire alarm systems level 1 exam Q
NICET fire alarm systems level 1 exam
Study online at https://quizlet.com/_7n3ypg
1. if a combination audible/visible appliances are in- the visible appliance
stalled, the location of the installed appliance shall be
determined by the requirements of
2. what is the maximum number of 12-gaugeTHHN con- 26
ductors that can be installed in 1-inch EMT
3. Do you resistors are connected in parallel. R1 = 300 150 Ohms
Ohms, R2 = 300 Ohms. What is the equivalent resis-
tance?
4. I room is 200 feet long and 100 feet wide, and the 8 12
foot high ceiling is smooth and flat. A spot-type heat
detector has been selected that is listed for a 50 foot
maximum spacing between detectors. According to
NFPA 72, how many detectors will be needed to protect
this room?
5. Fire warning equipment to be installed and residential ANSI S3.41
occupancy's child produced audible emergency evac-
uation signal described in
6. According to NFPA 72, the minimum number of restor- Two detectors are more on
able fixed-temperature spot-type heat detectors that each initiating device cir-
must be tested during each annual test is cuit
7. According to, how many spot type heat detectors are 6
required for a space that is 80 foot long and 55-foot
wide with a smooth 10 foot ceiling? The heat detector
is listed for a maximum space between detectors of 30
feet.
8. White
1/3
NICET fire alarm systems level 1 exam
Study online at https://quizlet.com/_7n3ypg
1. if a combination audible/visible appliances are in- the visible appliance
stalled, the location of the installed appliance shall be
determined by the requirements of
2. what is the maximum number of 12-gaugeTHHN con- 26
ductors that can be installed in 1-inch EMT
3. Do you resistors are connected in parallel. R1 = 300 150 Ohms
Ohms, R2 = 300 Ohms. What is the equivalent resis-
tance?
4. I room is 200 feet long and 100 feet wide, and the 8 12
foot high ceiling is smooth and flat. A spot-type heat
detector has been selected that is listed for a 50 foot
maximum spacing between detectors. According to
NFPA 72, how many detectors will be needed to protect
this room?
5. Fire warning equipment to be installed and residential ANSI S3.41
occupancy's child produced audible emergency evac-
uation signal described in
6. According to NFPA 72, the minimum number of restor- Two detectors are more on
able fixed-temperature spot-type heat detectors that each initiating device cir-
must be tested during each annual test is cuit
7. According to, how many spot type heat detectors are 6
required for a space that is 80 foot long and 55-foot
wide with a smooth 10 foot ceiling? The heat detector
is listed for a maximum space between detectors of 30
feet.
8. White