NICET 1 Fire Alarm
Study online at https://quizlet.com/_ct7hkc
1. NFPA 170 is the Standard that addresses what? Fire Protection Signs and Symbols
for architectural and engineering
drawings.
2. "F" Symbol stands for what? Fire Alarm Manual Pull
3. What drawings would show the interconnection Riser Drawings
of the detection devices and the control panel?
4. What are minimum requirements for system doc- Battery Calculations, Floor Plan,
umentation? Sequence of Operations, Voltage
Drop Calculations
5. All fire alarm system record documentation shall Documentation Cabinet
be stored ______.
6. The owner's manual shall include step-by-step in- TRUE!
structions detailing the testing and maintenance
procedures, and the intervals, at which these pro-
cedures shall be performed, for each type of de-
vice installed.
7. What document would you reference to deter- Input/output Matrix
mine if the appropriate outputs were activated
for a specific detector?
8. Which of the choices below does NFPA 72 recom- What is to be tested and how it is
mend be specified in the test plan? to be tested.
9. NFPA 72 Section 7.6.6 requires that the forms in False
Figures 7.8.2(g) through 7.8.2(l) be used for doc-
umenting the test results.
10. I/O Matrix
, NICET 1 Fire Alarm
NICET 1 Fire Alarm
Study online at https://quizlet.com/_ct7hkc
When testing the fire alarm system, the docu-
ment that defines what actions are taken when a
detector goes into alarm is the _____.
11. Trouble Circuits Monitor what? All device wiring for open conduc-
tors
All device wiring for shorts to
ground
The primary power supply
The secondary power supply
12. The secondary power supply must be capable of 10 Seconds
assuming the maximum load of the protected
premises system within ______.
13. The secondary power supply must be capable of 24 Hours
providing standby power to the fire alarm system
for ______.
14. At the end of the required standby period, the 5 Minuets
secondary power supply for a protected premises
system must be capable of operating the system
in full alarm mode for _____.
15. If the secondary power supply is providing power 15 Minuets
to an emergency voice communication system, it
must be able to operate the system in full alarm
mode for _____.
16. What chapter of NFPA 72 covers smoke detector Chapter 17
requirements?
17.