LP Gas Master Qualifier: Bulk Plants
Study online at https://quizlet.com/_9w7026
1. Bulk storage containers are to be equipped with which D. All of the above
of the following?
a. Pressure gauge
b. Liquid Level gauge
c. Relief valve
d. All of the above
2. Remote Shutdown Stations (ESV'S): Plant ESV located c. 25ft - 100ft
not less than ______ ft. and not more than _____ ft. from
point of transfer.
a. 20ft - 50ft
b. 25ft - 75ft
c. 25ft - 100ft
d. 50ft - 100ft
3. Correct color-coding of piping: 30 inches from a valve d. Red and Yellow
______for liquid piping and ______ for vapor piping.
a. Pink and Blue
b. Green and Orange
c. Black and White
d. Red and Yellow
4. Each industrial plant, bulk plant, and distributing point c. 18
shall be provided with at least one portable fire extin-
guisher in accordance with section 4.7 having a mini-
mum capacity of ____ lb. of dry chemical
a. 10
b. 12
c. 18
d. 30
1/3