Examination Advanced 100-Question
Practice Exam 2026 | Questions &
Answers with Detailed Rationales |
Complete Exam Prep & Study Guide
1. A refrigeration system uses a TXV and has a high superheat condition at the
evaporator outlet while the receiver contains adequate liquid refrigerant.
What is the most likely cause?
A. Excessive condenser subcooling
B. Insufficient refrigerant flow through the TXV
C. Oversized evaporator
D. Excessive compressor displacement
Rationale: A starved evaporator produces high outlet superheat. With liquid
available at the receiver, attention should focus on the TXV, its sensing bulb,
inlet strainer, or refrigerant feed restriction.
2. What is the primary purpose of maintaining liquid subcooling at the
condenser outlet in a conventional liquid-line system?
,A. Prevent compressor slugging
B. Increase suction pressure
C. Ensure solid liquid reaches the metering device
D. Reduce evaporator superheat
Rationale: Subcooling provides a margin against liquid flashing in the liquid line
before the metering device, helping maintain stable refrigerant feeding.
3. A compressor repeatedly trips on its internal overload after operating for
several minutes. The suction pressure is low and discharge pressure is also
below normal. Which condition is most likely?
A. Dirty condenser
B. Overcharged system
C. Low refrigerant charge or restricted refrigerant feed
D. Excessive ambient temperature
Rationale: Low suction pressure can reduce motor cooling in many compressors,
while low head pressure can accompany an undercharge or inadequate
refrigerant flow.
4. Why should a refrigeration contractor use a micron gauge during
evacuation rather than relying solely on a compound pressure gauge?
A. Compound gauges measure temperature
B. Micron gauges measure refrigerant weight
C. A micron gauge measures the very low absolute pressure needed to verify
deep evacuation
D. Compound gauges cannot measure positive pressure
Rationale: Evacuation must be verified at very low absolute pressures. A
standard compound gauge is not sufficiently sensitive for this purpose.
5. A system reaches 500 microns during evacuation but rises rapidly to 2,000
microns after the vacuum pump is isolated. What does this most strongly
indicate?
,A. Excessive condenser capacity
B. A leak or significant moisture/outgassing remaining in the system
C. Excessive liquid-line subcooling
D. Oversized compressor
Rationale: A rapid vacuum rise after isolation indicates that the system is not
holding the achieved vacuum. Leak checking and moisture-removal procedures
are required.
6. What is the principal reason a filter-drier is installed in a refrigeration
system?
A. Increase compressor displacement
B. Raise condensing temperature
C. Remove moisture, acids, and contaminants from the refrigerant circuit
D. Increase suction superheat
Rationale: Filter-driers protect the metering device and compressor by trapping
contaminants and removing moisture and, depending on design, acids.
7. A liquid-line filter-drier has a substantial temperature drop across it while
the system is operating. What condition should be suspected?
A. Oversized evaporator
B. Restricted filter-drier
C. Excessive compressor oil
D. Low condenser pressure
Rationale: A significant temperature difference across a liquid-line drier
indicates a pressure drop that can cause refrigerant flashing downstream and
may signify restriction.
8. What is the primary function of an accumulator installed in the suction
line?
A. Store liquid refrigerant for the condenser
B. Increase liquid-line pressure
, C. Prevent liquid refrigerant from entering the compressor
D. Increase condenser subcooling
Rationale: The accumulator separates and temporarily stores liquid refrigerant
returning from the evaporator, protecting the compressor from liquid slugging.
9. A refrigeration compressor has a low suction pressure, high superheat, and
normal-to-low condensing pressure. Which diagnosis is most appropriate?
A. Flooded evaporator
B. Starved evaporator
C. Dirty condenser
D. Overcharged system
Rationale: Low suction pressure combined with high superheat is characteristic
of insufficient refrigerant feed to the evaporator.
10.Why is compressor oil return particularly important in a low-temperature
refrigeration system?
A. Oil increases refrigerant pressure
B. Oil prevents condenser fouling
C. Oil must circulate back to the compressor to maintain proper lubrication
D. Oil eliminates the need for an accumulator
Rationale: Excessive oil remaining in the system can reduce heat-transfer
efficiency and leave the compressor oil-depleted, potentially causing mechanical
failure.
11.What is the most important reason a TXV sensing bulb must be firmly
attached and properly insulated where required?
A. To increase liquid pressure
B. To accurately sense suction-line temperature and control refrigerant flow
C. To reduce condenser pressure
D. To prevent liquid-line migration