A fire department access road is permitted to be what maximum distance
from any portion of the exterior wall of a building
- accurate answers-150 Ft
What is the class of an interior wall and ceiling finish that has a flame spread
index of 38 and a smoke developed index of 150
- accurate answers-Class b
What is the minimum frequency that employees of airport traffic control
towers be instructed on an emergency action plan
- accurate answers-Annual
How often do pipes and fittings for a dry system need to be inspected
- accurate answers-Annual
A vocational tech school has a woodworking shop used for educational
purposes. What is the occupant load factor for this type of use
- accurate answers-50 net ft
What minimum total combined hose stream allowance is required for a
hydraulically calculated sprinkler system protecting an extra hazard area
- accurate answers-500 gpm
Foam agents are most common to what class of fires?
- accurate answers-Class A and B
When operated at maximum speed fully open indicating valves must remain
open for what minimum amount of time before closing
- accurate answers-5 seconds
How much advance notice is required when inspector is investigating a
complaint concerning serious fire and life safety violations
- accurate answers-No advance notice is required
, What is the maximum occupant load allowed for an existing sprinkler two
story assembly occupancy of type ll [000] construction
- accurate answers-300
When dots an inspector have the authority to order occupants to vacate a
building
- accurate answers-If an immediate danger exist
Which of the following is a verbal affirmation or declaration made under oath
in a court of law
- accurate answers-Testimony
Which stage of a fire within a compartment does the fuel source produce some
heat but has not yet spread to other substances nearby
- accurate answers-Incipient
An automatic sprinkler system is required in an airport terminals concourse
when it exceeds what total floor area
- accurate answers-12,000 ft
Which of the following is describe as the propagation of a flame over a surface
- accurate answers-Flame spread
Which flammable and combustible liquids must be stored in a closed tanks or
containers when not in use and ambient or process temperatures are at or
above their flash points
- accurate answers-Class II and III
Manual fire alarm box shall be located within how many inches of exit
doorways
- accurate answers-60 inches
How often do monitor nozzles used with private service mains need to be
inspector
- accurate answers-Semiannual
What is the maximum amount of lumber permitted to be stored in a lumber
yard before a permit is required
- accurate answers-100,000 board ft
Answers 2025\2026 A+ Grade.
A fire department access road is permitted to be what maximum distance
from any portion of the exterior wall of a building
- accurate answers-150 Ft
What is the class of an interior wall and ceiling finish that has a flame spread
index of 38 and a smoke developed index of 150
- accurate answers-Class b
What is the minimum frequency that employees of airport traffic control
towers be instructed on an emergency action plan
- accurate answers-Annual
How often do pipes and fittings for a dry system need to be inspected
- accurate answers-Annual
A vocational tech school has a woodworking shop used for educational
purposes. What is the occupant load factor for this type of use
- accurate answers-50 net ft
What minimum total combined hose stream allowance is required for a
hydraulically calculated sprinkler system protecting an extra hazard area
- accurate answers-500 gpm
Foam agents are most common to what class of fires?
- accurate answers-Class A and B
When operated at maximum speed fully open indicating valves must remain
open for what minimum amount of time before closing
- accurate answers-5 seconds
How much advance notice is required when inspector is investigating a
complaint concerning serious fire and life safety violations
- accurate answers-No advance notice is required
, What is the maximum occupant load allowed for an existing sprinkler two
story assembly occupancy of type ll [000] construction
- accurate answers-300
When dots an inspector have the authority to order occupants to vacate a
building
- accurate answers-If an immediate danger exist
Which of the following is a verbal affirmation or declaration made under oath
in a court of law
- accurate answers-Testimony
Which stage of a fire within a compartment does the fuel source produce some
heat but has not yet spread to other substances nearby
- accurate answers-Incipient
An automatic sprinkler system is required in an airport terminals concourse
when it exceeds what total floor area
- accurate answers-12,000 ft
Which of the following is describe as the propagation of a flame over a surface
- accurate answers-Flame spread
Which flammable and combustible liquids must be stored in a closed tanks or
containers when not in use and ambient or process temperatures are at or
above their flash points
- accurate answers-Class II and III
Manual fire alarm box shall be located within how many inches of exit
doorways
- accurate answers-60 inches
How often do monitor nozzles used with private service mains need to be
inspector
- accurate answers-Semiannual
What is the maximum amount of lumber permitted to be stored in a lumber
yard before a permit is required
- accurate answers-100,000 board ft