Answers – Complete Exam latest update
this year
Introduction
This document contains multiple-choice medical gas refresher
questions and answers covering bulk systems, cryogenic fluid
supply systems, medical air, oxygen systems, vacuum
filtration, piping requirements, alarms, and ASSE certification
topics. It is designed to support exam preparation with precise
answers and NFPA 99 code references. The material includes
medical gas installation, testing, and safety requirements
commonly assessed in certification and refresher
examinations.
Exam Questions and Answers
WHICH OF THE FOLLOWING IS REQUIRED FOR CONTROL
EQUIPMENT OF A BULK SYSTEM THAT IS INSTALLED
REMOTELY FROM THE SOURCE SUPPLY
A) DIRECT HEATING
B) ELECTRICAL OUTLETS 5' ABOVE FLOOR
, C) LOCAL ALARM
D)ABILITY TO BE SECURED AND LOCKED --- correct precise
answer ---D)ABILITY TO BE SECURED AND LOCKED 5.1.3.4
CARBON DIOXIDE CYLINDERS SHALL BE PREVENTED FROM
REACHING TEMPERATURES OF
A) 110 DEG F
B) 125 DEG F
C) 35 DEG F
D) 135 DEG F --- correct precise answer ---B) 125 DEG F
5.1.3.2.13
NITROUS OXIDE CYLINDERS SHALL BE PREVENTED FROM
EXCEED TEMPERATURES LOWER THAN
A) 52° F
B) 7° F
C) 20° F
D) 125° F --- correct precise answer ---C) 20° F 5.1.3.2.13
COMPUTER SYSTEMS USED AS SUBSTITUTE MASTER ALARMS
SHALL BE PERMITTED
A) TRUE
B) FALSE --- correct precise answer ---A) TRUE 5.1.9.3
IN POTENTIALLY DAMP LOCATION, COPPER TUBE HANGERS
AND SUPPORTS SHALL BE
A) COPPER
B) WRAPPED WITH TAPE