✔✔Tanks shall be installed in accordance with - ✔✔NFPA 22
✔✔Each remote fire department connection shall be designated by a sign as follows: -
✔✔-sign shall have a raised or engraved letters at least 1 inch in height on a plate or
fitting.
-The sign shall indicate the type of system for which the connection is intended.
✔✔Where post indicator valves are used, they shall be set so that the top of each post
is - ✔✔32-40 inches above final grade
✔✔The connection from the hydrant to the main shall not be less than - ✔✔6 inches
✔✔Hydrants shall be located not less than _______ from the building to be protected -
✔✔40ft
✔✔Where hydrants located closer than 40ft to the building, shall be permitted to be
used where approved by - ✔✔the AHJ
✔✔The center of a hose outlet shall not be less than_______above final grade - ✔✔18
inches
✔✔The center of a hose outlet shall not be more than_______above final grade - ✔✔36
inches
✔✔The center of a hose outlet located in a hose house shall not be less than _______
above the floor - ✔✔12 inches
✔✔Master streams shall be delivered by monitor nozzles, hydrant-mounted monitor
nozzles, and similar master stream equipment capable of delivering more than - ✔✔250
GPM ( 950 LPM)
✔✔The top of the pipe shall not be buried less than _______ nelow the frost line for the
locality. - ✔✔12 Inches
✔✔In locations where freezing is not a factor, the depth cover shall not be less than
______ below grade to prevent mechanical damage. - ✔✔30 Inches
✔✔Private fire service mains installed under driveways or roadways shall be buried at a
minimum depth of - ✔✔36 inches
QUESTIONS AND SOLUTIONS RATED A+
✔✔Tanks shall be installed in accordance with - ✔✔NFPA 22
✔✔Each remote fire department connection shall be designated by a sign as follows: -
✔✔-sign shall have a raised or engraved letters at least 1 inch in height on a plate or
fitting.
-The sign shall indicate the type of system for which the connection is intended.
✔✔Where post indicator valves are used, they shall be set so that the top of each post
is - ✔✔32-40 inches above final grade
✔✔The connection from the hydrant to the main shall not be less than - ✔✔6 inches
✔✔Hydrants shall be located not less than _______ from the building to be protected -
✔✔40ft
✔✔Where hydrants located closer than 40ft to the building, shall be permitted to be
used where approved by - ✔✔the AHJ
✔✔The center of a hose outlet shall not be less than_______above final grade - ✔✔18
inches
✔✔The center of a hose outlet shall not be more than_______above final grade - ✔✔36
inches
✔✔The center of a hose outlet located in a hose house shall not be less than _______
above the floor - ✔✔12 inches
✔✔Master streams shall be delivered by monitor nozzles, hydrant-mounted monitor
nozzles, and similar master stream equipment capable of delivering more than - ✔✔250
GPM ( 950 LPM)
✔✔The top of the pipe shall not be buried less than _______ nelow the frost line for the
locality. - ✔✔12 Inches
✔✔In locations where freezing is not a factor, the depth cover shall not be less than
______ below grade to prevent mechanical damage. - ✔✔30 Inches
✔✔Private fire service mains installed under driveways or roadways shall be buried at a
minimum depth of - ✔✔36 inches