When calculations in Article 220 result in a fraction of an ampere that is less than _____, such fractions
can be dropped. - correct answer .5
The 3 VA per square foot general lighting load for dwelling units does not include _____. - correct
answer all
Where a building is designed and constructed to comply with an energy code adopted by the local
authority and specifying an overall lighting density of less than 1.20 VA per 1.20 sq ft, the unit lighting
loads in Table 220.12 for office and bank areas within the building shall be permitted to be reduced by
_____ VA per sq ft. - correct answer 1
Where fixed multioutlet assemblies are used in other than dwelling units or the guest rooms of hotels or
motels, each _____ or fraction thereof of each separate and continuous length shall be considered as
one outlet of not less than 180 VA where appliances are unlikely to be used simultaneously. - correct
answer 5 ft
For other than dwelling occupancies, banks, or office buildings, each receptacle outlet shall be
calculated at not less than _____ VA. - correct answer 180
A device comprised of _____ or more receptacles shall be calculated at not less than 90 VA per
receptacle. - correct answer four
The 3 VA per square foot general lighting load for dwelling units includes general use receptacles and
lighting outlets. - correct answer True