1. According to the ASME Boiler and Pressure Vessel Code (BPVC), Section I, a "power boiler" is defined
as a boiler in which steam or other vapor is generated at a pressure exceeding:
• A) 0 psi
• B) 15 psi
• C) 30 psi
• D) 100 psi
• Answer: B
• Rationale: ASME BPVC Section I defines a power boiler as one where steam or vapor is
generated at pressures exceeding 15 psi for use external to itself .
2. The primary purpose of a safety valve on a steam boiler is to:
, Page 2 of 159
• A) Control the operating pressure
• B) Relieve excess pressure to prevent over-pressurization and rupture
• C) Regulate the water level
• D) Vent gases during startup
• Answer: B
• Rationale: Safety valves are critical overpressure protection devices designed to open
automatically at a set pressure and discharge enough steam to prevent pressure from rising
more than a specified amount above the MAWP .
3. What is the minimum number of safety valves required on a boiler with more than 500 square feet of
heating surface?
• A) One
• B) Two
• C) Three
, Page 3 of 159
• D) Four
• Answer: B
• Rationale: ASME Code typically requires at least two safety valves for boilers with over 500 sq ft
of heating surface to ensure adequate relieving capacity and redundancy .
4. The device used to automatically add feedwater to a boiler in response to changing water level is a:
• A) Pressure reducing valve
• B) Feedwater regulator
• C) Blowdown valve
• D) Safety valve
• Answer: B
• Rationale: A feedwater regulator (or feedwater controller) automatically controls the feed pump
or feed valve to maintain the boiler water level within normal limits .
, Page 4 of 159
5. The process of removing sediment and concentrated solids from the bottom of a boiler is called:
• A) Surface blowdown
• B) Bottom blowdown
• C) Skimming
• D) Scavenging
• Answer: B
• Rationale: Bottom blowdown involves opening valves on the bottom of the boiler or water drum
to remove sludge, sediment, and precipitated solids that settle at the lowest points .
6. A "hydrostatic test" on a boiler is performed using:
• A) Steam at operating pressure
• B) Air at 1.5 times MAWP
• C) Water at 1.5 times MAWP
• D) Oil at design pressure