QUESTIONS AND CORRECT ANSWERS
◉ Atmospheric pressure in psi.
Answer: 14.7 psi
◉ Atmospheric pressure in in.Hg..
Answer: 29.29 in.HG
◉ Lbs of air required to burn 1 lb of fuel.
Answer: 15 lbs
◉ % of oxygen in air.
Answer: 21%
◉ Lbs of air required to burn 1 lb of carbon.
Answer: 11.53 lbs
◉ Percentage of condensate return (Rc).
Answer: = [Mc-Fc)/(Mc - CC)] x 100
Mc = Make-up conductivity
,Fc = Feedwater conductivity
Cc = Condensate conductivity
◉ Conversion factor for grains per gallon to parts per million.
Answer: 17.1
◉ Weight of column of mercury in psi =.
Answer: = 13.57 x .433 x Height
◉ Formula for the horsepower requirement for a pump =.
Answer: (Q x 8.33 x H x sp.gr. ) / 33,000 x n
Q = flow rate in gpm
H = total head
sp.gr. = specific gravity of fluid being pumped
n = Pump efficiency
◉ 1 lb of chemical to 1000 gallons of water = x ppm.
Answer: 120 ppm
◉ Target pH for boiler water.
Answer: 10.5 - 11.0
, ◉ Target pH for condensate =.
Answer: 8.3
◉ Target for Total Dissolved Solids (TDS) in steam boiler water.
Answer: 2000 - 2500 micromhos
◉ Target for Total Dissolved Solids (TDS) in a hot water boiler.
Answer: 3500 micromhos
◉ Water Horsepower =.
Answer: = (Q x H) / 3960
Q = flow rate in gpm
H = Head
◉ Flow rate of a pump (Q) =.
Answer: = (3960 x WHP) / H
Q = flow rate
WHP = water horsepower
H = Head
◉ Solve for total head for a pump =.
Answer: = (3960 x WHP) / Q