NASCLA ELECTRICAL CERTIFICATION
SCRIPT 2026 COMPLETE QUESTIONS AND
CORRECT ANSWERS
◉In kitchens, family rooms, and other similar rooms, receptacles
shall be installed so that no point measured horizontally along the
floor line of any wall space shall be more than ________ from a
receptacle outlet . Answer: 6' (210.52)
◉Receptacles located in or on floors shall not be counted as part of
the required number of receptacles unless located within . Answer:
18" of the wall (210.50)
◉It shall be permissible to apply a demand factor of ______ percent to
the nameplate rating load of four or more appliances fastened in
place, other than electric ranges, clothes dryers, space heating
equipment, or air-conditioning equipment, that are served by the
same feeder or service in a one family two family, or multifamily
dwelling. . Answer: 75% (220.53)
, ◉The load for household electric clothes dryers in a dwelling unit
shall be either ________ or the nameplate rating, whichever is larger
for each dryer served. . Answer: 5000w (220.54)
◉When two or more single phase dryers are supplied by a 3-phase
4-wire feeder or service, the total load shall be calculated on the
basis of ____________ the maximum number connected between any
two phases. . Answer: twice
◉It shall be permissible to calculate the load for commercial electric
cooking equipment, dishwasher booster heaters, water heaters, and
other kitchen equipment in accordance with table 220.56. The
demand factor for these units is ___________ percent for the first two
devices, and ____________ percent for the third and _________ percent for
the fourth. . Answer: 100, 90, 80
◉Kitchen equipment demand factors shall not apply for ___________,
____________, and _______________ equipment . Answer: Space heating,
ventilating, or air conditioning. (continuous)
◉Optional load calculations for dwellings allow for:
100% of the first 10kva plus 40% of the remainder of the following
loads:
_________ VA per square foot for general lighting and receptacles
SCRIPT 2026 COMPLETE QUESTIONS AND
CORRECT ANSWERS
◉In kitchens, family rooms, and other similar rooms, receptacles
shall be installed so that no point measured horizontally along the
floor line of any wall space shall be more than ________ from a
receptacle outlet . Answer: 6' (210.52)
◉Receptacles located in or on floors shall not be counted as part of
the required number of receptacles unless located within . Answer:
18" of the wall (210.50)
◉It shall be permissible to apply a demand factor of ______ percent to
the nameplate rating load of four or more appliances fastened in
place, other than electric ranges, clothes dryers, space heating
equipment, or air-conditioning equipment, that are served by the
same feeder or service in a one family two family, or multifamily
dwelling. . Answer: 75% (220.53)
, ◉The load for household electric clothes dryers in a dwelling unit
shall be either ________ or the nameplate rating, whichever is larger
for each dryer served. . Answer: 5000w (220.54)
◉When two or more single phase dryers are supplied by a 3-phase
4-wire feeder or service, the total load shall be calculated on the
basis of ____________ the maximum number connected between any
two phases. . Answer: twice
◉It shall be permissible to calculate the load for commercial electric
cooking equipment, dishwasher booster heaters, water heaters, and
other kitchen equipment in accordance with table 220.56. The
demand factor for these units is ___________ percent for the first two
devices, and ____________ percent for the third and _________ percent for
the fourth. . Answer: 100, 90, 80
◉Kitchen equipment demand factors shall not apply for ___________,
____________, and _______________ equipment . Answer: Space heating,
ventilating, or air conditioning. (continuous)
◉Optional load calculations for dwellings allow for:
100% of the first 10kva plus 40% of the remainder of the following
loads:
_________ VA per square foot for general lighting and receptacles