NFPA 72 Exam Questions and
Answers3
A fire alarm system with a pre-signal feature installed on the protected premises shall be pre-
permitted if - ANSWERS-Approved by the AHJ
A pressure supervisory signal-initiating device for a dry-pipe sprinkler system shall indicate -
ANSWERS-Both high and low pressure conditions
A seperate storage battery and separate automatic charger shall be provided for straight the
engine-driven generator and shall - ANSWERS-Not be used for any other purpose
The secondary power supply for in building mass notification system shall be capable of
operating the system during emergency conditions for ______________________ and shall be
capable of operating the system during emergency conditions for ____________________ at
minimum connected load - ANSWERS-24 hrs/ 15 mins
All fire alarm systems shall test free of ______________________ - ANSWERS-Grounds
The alarm audible signal pattern used to notify building occupants of the need to evacuate shall
be the standard alarm evacuation signal consisting of a(n) - ANSWERS-Three pulses temporal
pattern
If guards are used to protecting a notification appliance such as strop eight it shall - ANSWERS-
Be listed to be used with the appliance
Maintenance of household fire alarm systems be conducted - ANSWERS-According to the
manufacturer's instructions
Answers3
A fire alarm system with a pre-signal feature installed on the protected premises shall be pre-
permitted if - ANSWERS-Approved by the AHJ
A pressure supervisory signal-initiating device for a dry-pipe sprinkler system shall indicate -
ANSWERS-Both high and low pressure conditions
A seperate storage battery and separate automatic charger shall be provided for straight the
engine-driven generator and shall - ANSWERS-Not be used for any other purpose
The secondary power supply for in building mass notification system shall be capable of
operating the system during emergency conditions for ______________________ and shall be
capable of operating the system during emergency conditions for ____________________ at
minimum connected load - ANSWERS-24 hrs/ 15 mins
All fire alarm systems shall test free of ______________________ - ANSWERS-Grounds
The alarm audible signal pattern used to notify building occupants of the need to evacuate shall
be the standard alarm evacuation signal consisting of a(n) - ANSWERS-Three pulses temporal
pattern
If guards are used to protecting a notification appliance such as strop eight it shall - ANSWERS-
Be listed to be used with the appliance
Maintenance of household fire alarm systems be conducted - ANSWERS-According to the
manufacturer's instructions