Content preview

Existing S-12 COF is renewable and can be
UPGRADED to S-15 by taking T-15 exam


When the pump is in operation a small water leak on the pump bearings is desirable and should not be
considered a malfunction. Additionally, water should discharge from a ---- relief valve (electric pump) or
--- exchanger (diesel pump) while the fire pump is operating under a "no-flow" condition. - ANS -
circulation /heat



A sprinkler system is a - ANS -fire extinguishing system, other than a water mist system, that utilizes
water as the extinguishing agent.



Inspection, testing, servicing and other maintenance of sprinkler systems must be - ANS -personally
supervised and be performed in accordance with NFPA (National Fire Protection Association) #25 2011
edition.



All multiple dwellings, factories, office buildings, warehouses, stores and offices, theaters and music
halls, hospitals and asylums, and all public schools and other public buildings, churches and other places
where large numbers of persons are congregated for purposes of worship, instruction, amusement, and
all piers, bulkheads, wharves, pier sheds, bulkhead sheds or other waterfront structures shall provide -
ANS -fire extinguishers, buckets, axes, fire hooks, fire doors and other means of preventing and
extinguishing fires as the commissioner may direct.



Required fire protection systems shall be extended or altered as necessary to maintain and continued
protection whenever - ANS -the building or structure is altered. Systems not complying with this section
shall be considered to be impaired.



It shall be unlawful to install or maintain any fire protection system or device that has - ANS -the physical
appearance of fire protection equipment but that does not perform a fire protection function where it
may be confused with actual fire protection equipment. An example would be a CCTV camera that is
installed inside a shell that resembles a sprinkler head



SPRINKLER AND/OR STANDPIPE SYSTEM MAINTENANCE AND INSPECTIONS - ANS -

,1. Automatic and non-automatic sprinkler systems shall be inspected, tested and maintained as required
by NFPA #25 2011 edition by a competent person holding a S-12 Certificate of Fitness and employed or
contracted by the owner, to see that all parts of the system are in good working order, and that the Fire
Department connection(s), if any, are ready for immediate use by the Fire Department. A detailed
record shall be kept on the premises or other approved location, for a minimum of 3 years for
examination by any representative of the Fire Department. - ANS -



2.A supply of at least six extra sprinkler heads shall be kept available on the premises, to replace
promptly any fused or damaged sprinklers. Any head which has opened or has been damaged shall be
replaced immediately with sprinkler head of similar characteristics such as operating temperature,
orifice size, deflector orientation and thermal sensitivity. - ANS -



3. At least once every five years, the Fire Department connection or connections for a sprinkler system
shall be subjected to a hydrostatic pressure test to demonstrate its suitability for Fire Department use.
The test shall be arranged to be conducted by a Master Fire Suppression Piping Contractor in the
presence of a Fire Department representative.

The contractor shall be hired by the owner or the owner's representative. - ANS -



4.There shall be one or more employees or individuals contracted by the owner with a Certificate of
Fitness to inspect the sprinkler system following the standard of the NFPA 25 of 2011. - ANS -



Automatic and non-automatic sprinkler systems shall be inspected, tested and maintained as required
by NFPA #25 2011 edition by - ANS -competent person holding a S-12 Certificate of Fitness and
employed or contracted by the owner, to see that all parts of the system are in good working order, and
that the Fire Department connection(s), if any, are ready for immediate use by the Fire Department.



A detailed record shall be kept on the premises or other approved location, for a minimum of - ANS -3
years for examination by any representative of the Fire Department.



A supply of at least----extra sprinkler heads shall be kept available on the premises, to replace promptly
any fused or damaged sprinklers. - ANS -6

,Any head which has ----or has been----1. shall be replaced immediately with sprinkler head of similar
characteristics such as operating temperature, orifice size, deflector orientation and thermal sensitivity.
- ANS -opened/damaged



At least once every ---- years - ANS -Fire Department connection or connections for a sprinkler system
shall be subjected to a hydrostatic pressure test to demonstrate its suitability for Fire Department use.



At least once every five years, the Fire Department connection or connections for a sprinkler system
shall be subjected to a hydrostatic pressure test to demonstrate its suitability for Fire Department use.
The test shall be arranged to be conducted by a ----by a----The contractor shall be hired by----- - ANS -
Master Fire Suppression Piping Contractor/1. a Fire Department representative/the owner or the
owner's representative.



There shall be---more employees or individuals contracted by the owner with a----Certificate of Fitness
1. inspect the sprinkler system following the standard of the NFPA 25 of 2011. - ANS -one/COF



II. RESPONSIBILITY OF THE BUILDING OWNER - ANS -



It shall be the -----'s responsibility to maintain the sprinkler system and to determine the individual
qualifications and competencies of the COF holder that performs the functions related to inspection,
testing and maintenance of such system. - ANS -owner's



The building owner shall assign an ----to comply with the requirements of study material. - ANS -
impairment coordinator



The impairment coordinator shall take the action(s) when - ANS -a standpipe system, sprinkler system or
fire alarm system is out of service.



The impairment coordinator shall maintain records of all - ANS -system inspections, tests, servicing and
other items of maintenance



The impairment coordinator's records of system inspections, tests, servicing and other items of
maintenance shall be kept on the premises or other approved location for a minimum of --- and made
available for inspection by any member of---- - ANS -3 years/FDNY

, In absence of a specific designee,the ---shall be considered the impairment coordinator. - ANS -building
owner



III. OUT OF SERVICE SYSTEMS (OOS) - ANS -



Planned removal from service: When the system, or a portion of the sprinkler system, is placed out of
service for a scheduled inspection, testing, regular maintenance, minor repairs or for construction
affecting not more than 1 floor, the ---- and ----of and authorize the placing of the system out of service.
- ANS -COF holder/impairment coordinator



Unplanned out of service condition - ANS -A serious defect in the sprinkler system including, but not
limited to: an empty tank, a break or major leak in the system's water piping, inoperative or shut water
supply valves, defective fire department connections, construction related shut downs affecting more
than one floor, or complete or partial shut downs of the sprinkler system, other than a shut down for a
planned removal from service



When a Fire Protection system is out of service fire watch personnel must: - ANS -• Continuously patrol
the area affected by the out-of-service fire protection system to which such person has been assigned,
keeping constant watch for fires.

• Be provided with at least one approved means for notification of the Fire Department and emergency
preparedness staff.

• Immediately report any fire to the Fire Department and notify emergency preparedness staff on
premises.

• Be trained in the used of portable fire extinguisher.

10

• Be responsible for extinguishing fires limited in size and spread that can be readily extinguished.

• Maintain a record of such fire watch on the premises during the fire watch and for a minimum of 48
hours after the fire watch has concluded.

• Have no other duties.



FIRE DEPARTMENT NOTIFICATIONS FOR OUT OF SERVICE CONDITIONS: - ANS -
$14.99
Get access to the full document:

100% satisfaction guarantee
Immediately available after payment
Both online and in PDF
No strings attached

Get to know the seller
Seller avatar
Lectcaptain

Get to know the seller

Seller avatar
Lectcaptain Chamberlain College Of Nursing
View profile
Follow You need to be logged in order to follow users or courses
Sold
2
Member since
8 months
Number of followers
0
Documents
594
Last sold
5 days ago
TOPNOTCH EXAM GUIDES

In need of study guides and wondering where and when to get them? Worry no more because I\'ve got you. Access actual tests 100% verified. ATI, NURSING, PMHNP, TNCC, USMLE, ACLS, WGU AND ALL EXAMS guaranteed success. Here, you will find everything you need in NURSING EXAMS AND TESTBANKS. Contact us, to fetch it for you in minutes if we do not have it in this shop. BUY WITHOUT DOUBT!!!!Always leave a review after purchasing any document so as to make sure our customers are 100% satisfied.

Read more Read less
0.0

0 reviews

5
0
4
0
3
0
2
0
1
0

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Frequently asked questions