Section 1: Fire Pump Components (10 Questions)
1. What is the primary function of a fire pump relief valve?
A) To maintain minimum pressure in the system B) To prevent overpressurization of the system
C) To increase flow rate during demand D) To bypass the pump during testing
Answer: B) To prevent overpressurization of the system Rationale: NFPA 20 (9.2.3) requires
relief valves to protect the system from excessive pressure.
2. Which component is responsible for preventing water from flowing back into
the pump after shutdown?
A) Pressure gauge B) Check valve C) Flow meter D) Suction strainer
Answer: B) Check valve Rationale: Check valves are installed to prevent backflow and maintain
system pressure.
3. The packing gland in a fire pump is used to:
A) Increase pump efficiency B) Prevent air from entering the pump C) Seal the shaft to prevent
water leakage D) Regulate pump speed
Answer: C) Seal the shaft to prevent water leakage Rationale: Packing glands prevent water
from leaking along the pump shaft.
4. What is the purpose of the suction strainer in a fire pump?
,A) To increase water velocity B) To prevent debris from entering the pump C) To measure
suction pressure D) To regulate pump flow
Answer: B) To prevent debris from entering the pump Rationale: Suction strainers protect the
pump from damage caused by debris.
5. Which of the following is NOT a component of a centrifugal fire pump?
A) Impeller B) Volute C) Piston D) Casing
Answer: C) Piston Rationale: Centrifugal pumps use impellers, not pistons.
6. The casing relief valve is designed to:
A) Increase pump efficiency B) Protect the pump from thermal damage C) Prevent cavitation D)
Regulate discharge pressure
Answer: C) Prevent cavitation Rationale: Casing relief valves prevent damage from cavitation
by maintaining minimum flow.
7. What does the pressure maintenance (jockey) pump do?
A) Provides primary fire protection flow B) Maintains system pressure during minor leaks C)
Replaces the main fire pump during testing D) Increases pump speed during demand
Answer: B) Maintains system pressure during minor leaks Rationale: Jockey pumps maintain
pressure and prevent unnecessary main pump starts.
8. The controller for an electric motor-driven fire pump must be:
A) Manually operated B) Listed for fire pump service C) Connected to the building’s main power
D) Located in a separate building
Answer: B) Listed for fire pump service Rationale: NFPA 20 (10.5.1) requires controllers to be
listed for fire pump duty.
, 9. What is the purpose of the flow meter in a fire pump system?
A) To measure pump efficiency B) To indicate the rate of water flow C) To regulate pump speed
D) To prevent cavitation
Answer: B) To indicate the rate of water flow Rationale: Flow meters provide real-time flow data
during testing and operation.
10. The suction pipe for a fire pump must be sized to:
A) Match the discharge pipe diameter B) Prevent cavitation and ensure adequate flow C)
Increase pump speed D) Reduce system pressure
Answer: B) Prevent cavitation and ensure adequate flow Rationale: NFPA 20 (4.15) specifies
suction pipe sizing to prevent cavitation.
Section 2: Diesel Engine Fire Pumps (10 Questions)
11. What is the minimum fuel supply required for a diesel fire pump?
A) 1 gallon per horsepower B) 1 gallon per hour of operation C) Enough for 8 hours of full-load
operation D) Enough for 24 hours of standby
Answer: C) Enough for 8 hours of full-load operation Rationale: NFPA 20 (11.2.3) requires fuel
for 8 hours at full load.
12. Diesel fire pumps must be tested weekly for:
A) Fuel consumption B) Battery voltage C) Automatic start and run D) Oil pressure
Answer: C) Automatic start and run Rationale: NFPA 25 (8.3.1) requires weekly automatic start
tests.
13. What is the purpose of the battery charger on a diesel fire pump?
A) To start the engine B) To maintain battery charge during standby C) To increase engine RPM
D) To regulate fuel flow