100% satisfaction guarantee Immediately available after payment Both online and in PDF No strings attached 4.6 TrustPilot
logo-home
Exam (elaborations)

MASSACHUSETTS OIL BURNER LICENSE NEWEST 2025 ACTUAL EXAM TEST BANK ( 3 VERSIONS) QUESTIONS AND CORRECT DETAILED ANSWERS (VERIFIED ANSWERS) |ALREADY GRADED A+

Rating
-
Sold
-
Pages
84
Grade
A+
Uploaded on
23-04-2025
Written in
2024/2025

MASSACHUSETTS OIL BURNER LICENSE NEWEST 2025 ACTUAL EXAM TEST BANK ( 3 VERSIONS) QUESTIONS AND CORRECT DETAILED ANSWERS (VERIFIED ANSWERS) |ALREADY GRADED A+

Institution
Massachusetts Oil Burner License
Course
Massachusetts oil burner license











Whoops! We can’t load your doc right now. Try again or contact support.

Written for

Institution
Massachusetts oil burner license
Course
Massachusetts oil burner license

Document information

Uploaded on
April 23, 2025
Number of pages
84
Written in
2024/2025
Type
Exam (elaborations)
Contains
Questions & answers

Subjects

Content preview

MASSACHUSETTS OIL BURNER LICENSE NEWEST 2025
ACTUAL EXAM TEST BANK ( 3 VERSIONS) QUESTIONS
AND CORRECT DETAILED ANSWERS (VERIFIED
ANSWERS) |ALREADY GRADED A+

What is flashpoint an indicator of? - ANSWERS-Minimum temperature oil will ignite but not
continue to burn.

What travels on the inside of the wire? - ANSWERS-Volts

What does readily accessible mean pertaining to oil burning equipment? - ANSWERS-
Capable of being reached easily and quickly for operation, maintenance or inspection.

What is the minimum vent pipe on an oil tank? - ANSWERS-1 1/4"

What causes corrosion on a flue pipe? - ANSWERS-When the flue pipe is operating below
the dew point temperature.

What are the methods to prevent oil waxing? - ANSWERS-Put additives in the fuel.

Add an oil line heater.

Cut with #1 fuel or kerosene.

What is the maximum tank size allowed inside unenclosed? - ANSWERS-660 gal

What is the purpose of a delayed oil valve? - ANSWERS-Allows time for the oil pump to get
up to speed.

Delays oil flow to the nozzle.

On a call where a hydronic heat system is putting out too much heat, the issue could be? -
ANSWERS-A shorted out thermostat.



What is the first thing a tech should do when arriving at a no combustion call? -
ANSWERS-Ask how many times the customer reset the unit.

What is the best long term solution for preventing a clogged nozzle? - ANSWERS--Remove
any underground storage tanks.
-Install a quality oil filter.
-Cut the suction line 10" above the tank outlet to prevent sludge.

Hot water and steam valves are interchangeable. - ANSWERS-False

,When in the presence of a flame, a cad cell normally reads.. - ANSWERS-300-1000 ohms

If a pump is used to bring oil to a level higher than the tank, an oil safety valve is required. -
ANSWERS-True

On a call where a hydronic heat system is putting out too much heat on the stack, the issue
may be.. - ANSWERS--Too much draft.
-Not enough combustion air in the equipment room.
-Air leakage into chamber.

A high CO2 reading is caused by.. - ANSWERS-Incomplete combustion

An often overlooked cause of a high CO2 reading is.. - ANSWERS-Not enough combustion
air in the equipment room.

When multiple pumps are wired together in a heating system, they should be wired in.. -
ANSWERS-parallel

In a series circuit.. - ANSWERS-Current has one path.

When 2 burners are connected to the same chimney.. - ANSWERS-Sufficient draft must be
obtained to operate both units.

The ignition transformer is located.. - ANSWERS-In the primary control.

When safeties are wired in series one safety will affect the operation of the others. -
ANSWERS-True

A stack switch is no longer allowed to be installed or replaced because.. - ANSWERS-It's
safety cutout time is higher than what is now required.

What is a power venter and what does it do? - ANSWERS-An electrical device that sends
fluid gases into the chimney connector.

A burner in a confined space using 1 GPH of #2 fuel oil requires what size permanent
opening for combustion air? - ANSWERS-140"

The difference between an adjustable flame retention burner and a fixed flame retention
burner is? - ANSWERS-Air inlets can be adjusted

Ignitor position can be adjusted

Fuel can be adjusted

Oil tank design, construction, installation and testing shall be in accordance with.. -
ANSWERS-527 CMR 9.0

Heat is a form of.. - ANSWERS-Energy

,If a burner is operational but the circulator pump isn't running.. - ANSWERS-The pump
relay is not working correctly

A method of dealing with low viscosity/cold temps with #2 oil? - ANSWERS-Increase pump
pressure/ decrease nozzle size

What is needed at the outlet of an oil tank? - ANSWERS-Thermal safety valve

Where do you obtain an installation permit for oil burners? - ANSWERS-Fire Dept

How many Btu's approximately in 1 gal of #2 fuel oil? - ANSWERS-140,000 btu's

Solid state ignition is superior to spark because - ANSWERS-It is not affected by reduced
voltage

What is an installation? - ANSWERS-The complete setting in place, ready for operation, of
an oil burner appliance together with its accessories and equipment.

How far must a power vent terminate from an opening or window? - ANSWERS-4'

A pump in a one pipe system that is full of air can be self purged. - ANSWERS-False

List the minimum size of an oil supply line. - ANSWERS-3/8"

A material with electrons so loose it allows voltage to pass with little or no resistance.. -
ANSWERS-Is a conductor

If a high limit goes off, what does a low water switch do? - ANSWERS-Maintains water
temperature

When measuring a cad cell with the burner running and the ff terminals jumped out, what
should the cad cell reading be? - ANSWERS-1600 ohms

What are the possible causes of soot at or near the power venter? - ANSWERS-Incomplete
combustion

What is a possible side effect of air in a nozzle line? - ANSWERS-Soot

What is the cause if the cad cell is tripped on safety? - ANSWERS-Dirty cad cell

Faulty cad cell

No flame present

If a boiler is running but the water temperature is low? - ANSWERS-Undersized nozzle

If a boiler is at 30 psi and the relief valve opens? - ANSWERS-Expansion tank is
undersized

, Tank bladder is perforated

Tankless coil is leaking

Atomizing type burners were designed to burn which type of fuel? - ANSWERS-#2 oil

One gallon of #2 fuel oil contains approximately: - ANSWERS-140,000 BTU's

Pour point problems with outside above ground fuel tanks can be partially relived by: -
ANSWERS--Relocating the outside fuel filters and strainers to the inside
-Switching to #1 fuel oil
-Reducing the pour point of #2 fuel oil by blending it with #1 fuel oil

A fuel oil storage tank cannot be installed: - ANSWERS-In the furnace room within 5 feet of
the heating unit

The primary purpose of a fuel pump in a high pressure burner is to: - ANSWERS--Deliver
oil at a constant and regulated pressure to the nozzle
-Move oil from the tank to the pump
-Provide a screen to filter the oil

If the vacuum reading is substantially above the calculated reading, (with the burner
running) the cause may be: - ANSWERS--Plugged fuel filter
-Kinked oil supply line
-Check valve sticking

With most new flame retention burners, the motor speed is: - ANSWERS-3400 rpm

To check for a proper nozzle line cut-off, the pressure gauge is installed in the: -
ANSWERS-Nozzle port

Fuel units are generally set at the factory at: - ANSWERS-100 psi

The oil burner nozzle in a high pressure burner performs the following functions: -
ANSWERS--Atomizes the oil
-Provides a pattern of oil spray
-Delivers a fixed amount of oil

The nozzle flow rate, spray angle and pattern are directly related to: - ANSWERS--
Tangential slots
-Swirl chamber
-Orifice

Cold oil or high viscosity problems may be eliminated by: - ANSWERS--Increasing the
pump pressure and reducing the nozzle size
-Installing a nozzle line pre-heater

The following conditions or elements affect choosing the correct nozzle spray patterns: -
ANSWERS--Air-oil mixing design of the burner

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
BESTEXAMS Chamberlain College Of Nursing
View profile
Follow You need to be logged in order to follow users or courses
Sold
55
Member since
2 year
Number of followers
25
Documents
1026
Last sold
3 weeks ago

My mission is to be your LIGHT in a dark time. If you are anxious or struggling with EXAMS,In my page you will find latest Exams, Test Banks,Solutions Manual, Exam Elaboration, Discussions, Case Studies,Essays etc. I upload quality and verified documents at an affordable price. Help others to benefit from this study materials by leaving a review, SUCCESS.I really want my notes to be your GUIDE!!! I know these helped countless others pass and that is all I want for YOU! I have a ""Love It"" GUARANTEE A+!

Read more Read less
4.2

19 reviews

5
6
4
11
3
2
2
0
1
0

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.